background image

A “higher” than normal liquid pressure may point out a dirty
condenser coil, or non-condensibles in the system (not evacu-
ated properly) or a condenser fan motor not running at full
speed.

A “lower” than normal liquid pressure may point out an ineffi-
cient compressor (low head - high suction) or a low refrigerant
charge.

Check flare caps on Schrader fittings to be sure they are tight.
DO NOT OVERTIGHTEN (40-60 inch-lbs. maximum).

2 SPEED FAN OPERATION

CAUTION:  2 - 2.5 TON UNITS

Opens @ 70

°

F (drops to 850 RPM)

Closes @ 80

°

F (increases to 1075 RPM)

CAUTION:  3- 5 TON UNITS

Opens @ 70

°

F (drops to 575 RPM)

Closes @ 80

°

F (increases to 850 RPM)

INSTRUCTING THE OWNER

Assist owner with processing warranty cards. Review Owners
Guide and provide a copy for the owner guidance on proper
operation and maintenance. Instruct the owner or the operator
how to start, stop and adjust temperature setting.

When applicable, instruct the owner that the compressor is
equipped with a crankcase heater to prevent the migration of
refrigerant to the compressor during the “OFF” cycle. The
heater is energized only when the unit is not running. If the main
switch is disconnected for long periods of shut down, do not
attempt to start the unit 8 hours after the switch has been
connected. This will allow sufficient time for all liquid refrigerant
to be driven out of the compressor.

The installer should also instruct the owner on proper  opera-
tion and maintenance of all other system components.

INDICATIONS OF PROPER OPERATION

Cooling operation is the same as any conventional air condi-
tioning unit.

The following checks may be made to determine if the system

is operating properly:

1. The outdoor fan should be running, with warm air being

discharged from the top of the unit.

2. The indoor blower (furnace or air handler) will be operating,

discharging cool air from the ducts.

3. The vapor line at the outdoor unit will feel cool to the touch.

4. The liquid line at the outdoor unit will feel warm to the touch.

NOTICE TO OWNER

If unit is not operating properly, check the following items before
calling a serviceman:

1. Indoor section for dirty filter.

2. Outdoor section for leaf or debris blockage.

Eliminate problem, turn off the thermostat for 10 seconds and
attempt start. Wait 5 minutes. If system does not start, call
serviceman.

MAINTENANCE

1. Dirt should not be allowed to accumulate on the outdoor

coils or other parts in the air circuit. Clean as often as
necessary to keep the unit clean. Use a brush, vacuum
cleaner attachment, or other suitable means.

2. The outdoor fan motor is permanently lubricated and does

not require periodic oiling.

3. If the coil needs to be cleaned, it should be washed with

Calgon Coil Clean (mix one part Coil Clean to seven parts
water). Allow solution to remain on coil for 30 minutes
before rinsing with clean water. Solution should not be
permitted to come in contact with painted surfaces.

4. Refer to the furnace or air handler instructions for filter and

blower motor maintenance.

5. The evaporator coil drain pan should be inspected and

cleaned regularly to prevent odors and assure proper drain-
age.

CAUTION: IT IS UNLAWFUL TO KNOWINGLY VENT, RE-
LEASE OR DISCHARGE REFRIGERANT INTO THE OPEN
AIR DURING REPAIR, SERVICE, MAINTENANCE OR THE
FINAL DISPOSAL OF THIS UNIT.

WHEN THE SYSTEM IS FUNCTIONING PROPERLY AND
THE OWNER HAS BEEN FULLY INSTRUCTED, SECURE
THE OWNER’S APPROVAL.

550.36-N2Y

Unitary Products Group

11

Summary of Contents for H2DH024S06

Page 1: ...The unit should be installed in accordance with all national and local safety codes Limitations for the indoor unit coil and appropriate accessories must also be observed For piping limitations and a...

Page 2: ...ERHEAD NEC CLASS 2 WIRING Sit unit on rubber elevator grommets to reduce noise and allow for proper drainage FIGURE 1 TYPICAL INSTALLATION MODEL H2DH024 H2DH030 H2DH036 H2DH042 H2DH048 H2DH060 UNIT SU...

Page 3: ...shown Sweat coils are shipped with a standard orifice in a plastic bag attached to the liquid line connection The orifice that is shipped with the coil is based on the most sold combination but it ma...

Page 4: ...The total system refrigerant charge is retained within the outdoor unit during shipping and installation The re usable service valves are provided to evacuate and charge per this instruction Serious s...

Page 5: ...the vapor fitting with a wet rag and braze the vapor line connection The nitrogen flow should be exiting the system from the vapor service port connection After This connection has cooled remove the...

Page 6: ...H2DH060 UNITORIFICE S 61 63 65 75 78 78 81 84 90 93 93 96 FACTORYR 22 CHARGE LBS OZ SWEAT 5 7 5 0 7 12 8 0 11 14 13 0 INDOOR COIL COIL ORIFICE REQUIRED SYSTEM ORIFICE ADDITIONAL CHARGE OZ G3HC G1FC02...

Page 7: ...urate weighing device is available add refrigerant accordingly CAUTION Compressor damage will occurif system is improp erly charged On new system installations charge system per R 22 charge informatio...

Page 8: ...73 75 77 79 79 2 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 82 4 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 Saturation Temperature TABLE 5 Temperature and Pressure TEMP F PRESSU...

Page 9: ...re the thermostat is set to operate the compressor CAUTION An attempt to start the compressor without at least 8 hours of crankcase heat will damage the com pressor A warning label with an adhesive ba...

Page 10: ...0 60 65 70 75 80 85 90 95 SUCTION PRESSURE PSIG LIQUID PRESSURE PSIG 115 F O D AMBIENT 95 F O D AMBIENT 036 036 036 75 F O D AMBIENT 048 060 042 042 EXAMPLE H2DH036 unit with a 76 PSIG measured suc ti...

Page 11: ...mine if the system is operating properly 1 The outdoor fan should be running with warm air being discharged from the top of the unit 2 The indoor blower furnace or air handler will be operating discha...

Page 12: ...ducts Group P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in U S A Copyright by York International Corporation 1995 All Rights Reserved RPC 8M 695 66 Code SBY...

Reviews: