*
Data in accordance with Eurovent Rooftop program certification conditions
PT: Total Power; PC: Power absorbed by the compressor
WB: Wet-bulb temperature; TS: Dry bulb temperature.
1.12 ARH/ARD Output
1.12.1 ARH/ARD 045 Cooling capacities
Return air
Outdoor coil air temperature (TS)
Flow
m
3
/h
TH
ºC
27 ºC
35 ºC
46 ºC
PT
kW
PC
kW
Sensible power kW
PT
kW
PC
kW
Sensible power kW
PT
kW
PC
kW
Sensible power kW
Input temp. TS in indoor coil
Input temp. TS in indoor coil
Input temp. TS in indoor coil
30
27
24
22
30
27
24
22
30
27
24
22
(Mini‐
mum)
7000
23
53.7
11.1
31.8
25.2
18.6
-
50.9
12.2
30.8
41.3
17.6
-
45.9
13.5
29.2
22.6
16
-
19
48.6
10.8
41.7
35.1
28.5
24.1
45.9
11.7
40.6
24.2
27.4
23
41.3
12.6
39
32.3
25.7
21.3
17
45.9
10.5
45.9
40
33.3
32.5
42.2
11.6
42.2
34
31.6
29.2
37.6
12.5
37.6
36.3
29.8
25.4
15
41.3
10.4
41.3
41.3
36.9
32.5
39.5
11.3
39.5
38.2
36
31.6
35.3
12.4
35.3
35.3
34.2
29.8
(Nominal)
8500
23
55.7
11.3
34.9
27.1
19.2
-
52.8
12.4
33.9
26.1
18.3
-
47.6
13.7
32.3
24.5
16.6
-
19
50.5
10.9
46.6
38.8
30.9
25.7
47.6*
11.9*
45.5
37.6*
29.8
24.6
42.8
12.9
42.8
35.9
28.1
22.9
17
47.6
10.7
47.6
44.5
36.6
36.8
43.8
11.8
43.8
42.7
34.9
32.4
39
12.7
39
39
33
27.8
15
42.8
10.6
42.8
42.8
41.1
35.9
40.9
11.5
40.9
40.9
40.1
34.9
36.7
12.6
36.7
36.7
36.7
33.1
(Maxi‐
mum)
10000
23
57.25
11.5
37.9
28.9
19.8
-
54.3
12.6
37
27.9
18.8
-
48.9
213.9
35.3
26.3
17.2
-
19
51.8
11.1
51.3
42.2
33.2
27.2
48.9
12.1
48.9
41.1
32.1
26
44
13.1
44
39.4
30.3
24.3
17
48.9
10.9
48.9
48.8
39.7
41.3
45
12
45
45
37.9
35.6
40.1
12.9
40.1
40.1
36.1
30
15
44
10.8
44
44
44
39
42.1
11.7
42.1
42.1
42.1
38
37.6
12.8
37.6
37.6
37.6
36.2
*
Data in accordance with Eurovent Rooftop program certification conditions
PT: Total Power; PC: Power absorbed by the compressor
WB: Wet-bulb temperature; TS: Dry bulb temperature.
1.12.2 ARH/ARD 060 Cooling capacities
Return air
Outdoor coil air temperature (TS)
Flow
m
3
/h
TH
ºC
27 ºC
35 ºC
46 ºC
PT
kW
PC
kW
Sensible power kW
PT
kW
PC
kW
Sensible power kW
PT
kW
PC
kW
Sensible power kW
Input temp. TS in indoor coil
Input temp. TS in indoor coil
Input temp. TS in indoor coil
30
27
24
22
30
27
24
22
30
27
24
22
(Mini‐
mum)
9500
23
69.8
14.2
42.2
33.1
24.1
-
66.3
15.5
40.9
31.9
22.8
-
59.7
17.1
38.8
29.8
20.7
-
19
63.2
13.7
55.7
46.7
37.7
31.6
59.7
14.9
54.3
45.2
36.3
30.2
53.7
16.1
52.1
43
34
28
17
59.7
13.4
59.7
53.3
44.3
42.5
54.9
14.8
54.9
51
42
38.3
48.9
15.9
49
48.7
36.7
33.6
15
53.7
13.3
53.7
53.7
49.3
43.3
51.3
14.5
51.3
51.3
48
42
46
15.8
46
46
45.8
39.8
(Nomi‐
nal)
11500
23
72.4
14.4
46.5
35.8
25
-
68.7
15.8
45.2
34.5
23.8
-
61.9
17.5
43.2
32.4
21.7
-
19
65.6
14
62.4
51.7
41
33.8
61.9*
15.2*
61
50.3*
39.5
32.4
55.7
16.4
55.7
48
37.3
30.1
17
61.9
13.7
61.9
59.5
48.7
48.1
56.9
15
56.9
56.9
46.5
42.5
50.8
16.3
50.8
50.8
44.1
36.9
15
55.7
13.5
55.7
55.7
55
47.8
53.2
14.7
53.2
53.2
53.2
46.5
47.7
16.1
47.7
47.7
47.7
44.2
(Maxi‐
mum)
13500
23
74.4
14.6
50.7
38.2
25.8
-
70.6
16
49.4
37
24.6
-
63.6
17.7
47.3
34.9
22.5
-
19
67.4
14.2
67.4
56.5
44.1
35.8
63.6
15.4
63.6
55.1
42.6
34.3
57.2
16.6
57.2
52.8
40.2
32.1
17
63.6
13.9
63.6
63.6
53
53
58.5
15.2
58.5
58.5
50.8
46.6
52.1
16.5
52.1
52.1
48.3
40
15
57.2
13.7
57.2
57.2
57.2
52.1
54.7
14.9
54.7
54.7
54.7
50.8
49
16.3
49
49
49
48.6
*
Data in accordance with Eurovent Rooftop program certification conditions
PT: Total Power; PC: Power absorbed by the compressor
WB: Wet-bulb temperature; TS: Dry bulb temperature.
Installation manual
1
ARH/ARD Output 1.12
15
Summary of Contents for ARC 045
Page 1: ...ACTIVA SERIES ROOF TOP Air Conditioners Installation manual Ref N 40XXX...
Page 2: ......
Page 5: ...1 Installation manual...
Page 46: ......
Page 47: ...2 Unit installation data...
Page 52: ......