J. Power cable intake (∅ 38 + 29 mm) (side)
K. Opening for connection of lower supply and return air ducts.
L. Control cable intake (PG 21 mm) (lower)
M. Power cable intake (PG 48 mm) (lower)
N. Close-up of the base, shown separately to be more easily seen
O. Access to filters and indoor coil
P. Condensate drain connection (1” BSP Female)
Q. Access to the outdoor air compartment
R. Supply and return air compartment side panels See
Connections for supply and return side
ducts
, ver pág. 10
S. Compressor access
T. Pressure reading connection
1. Return air
2. Supply air
3. Condensate air
1.11 ARC/ARG Performance
1.11.1 ARC/ARG 045 Cooling capacities
Return air
Outdoor coil air temperature (TS)
Flow
m
3
/h
TH
ºC
27 ºC
35 ºC
46 ºC
PT
KW
PC
kW
Sensible power kW
PT
kW
PC
kW
Sensible power kW
PT
kW
PC
kW
Sensible power kW
Input temp. TS in indoor coil
Input temp. TS in indoor coil
Input temp. TS in indoor coil
30
27
24
22
30
27
24
22
30
27
24
22
(Mini‐
mum)
7000
23
50.9
10.9
29.4
23.5
17.6
-
48.3
12
28.5
22.6
16.7
-
43.5
13.2
26.9
21
15.1
-
19
46.1
10.6
38.3
32.5
26.6
22.7
43.5
11.5
37.3
31.4
25.5
21.6
39.1
12.4
35.6
29.8
23.9
19.9
17
43.5
10.4
42.7
36.8
30.9
35.6
40
11.4
40
35.1
29.2
30.4
35.7
12.3
35.7
33.4
27.5
23.5
15
39.1
10.2
39.1
39.1
34.1
30.1
37.4
11.2
37.4
37.4
33.1
29.2
33.5
12.2
33.5
33.5
31.5
27.5
(Nominal)
8500
23
52.8
11.1
32
25.1
18.2
-
50.1
12.2
31.1
24.2
17.3
-
45.1
13.5
29.5
22.6
15.7
-
19
47.8
10.8
42.4
35.5
28.6
24
45.1*
11.7*
41.3
34.4*
27.5
22.9
40.6
12.6
39.7
32.7
25.8
21.2
17
45.1
10.5
45.1
40.5
33.6
41.3
41.5
11.6
41.5
38.9
31.9
34
37
12.5
37
37
30.2
25.6
15
40.6
10.4
40.6
40.6
37.5
32.9
38.8
11.3
38.8
38.8
36.5
31.9
34.7
12.4
34.7
34.7
34.7
30.2
(Maxi‐
mum)
10000
23
54.1
11.3
34.5
26.6
18.7
-
51.4
12.4
33.5
25.7
17.8
-
46.3
13.7
32
24.1
16.2
-
19
49.1
10.9
46.2
38.3
30.4
25.2
46.3
11.9
45.1
37.2
29.3
24.1
41.7
12.9
41.7
35.6
27.7
22.4
17
46.3
10.7
46.3
44
36.2
46.3
42.6
11.8
42.6
42.3
34.4
37.4
38
12.7
38
38
38
27.4
15
41.7
10.6
41.7
41.6
40.7
35.4
39.8
11.5
39.8
39.8
39.7
34.5
35.7
12.6
35.7
35.7
35.7
32.8
*
Data in accordance with Eurovent Rooftop program certification conditions
PT: Total Power; PC: Power absorbed by the compressor
WB: Wet-bulb temperature; TS: Dry bulb temperature.
1.11.2 ARC/ARG 060 Cooling capacities
Return air
Outdoor coil air temperature (TS)
Flow
m
3
/h
TH
ºC
27 ºC
35 ºC
46 ºC
PT
kW
PC
kW
Sensible power kW
PT
kW
PC
kW
Sensible power kW
PT
kW
PC
kW
Sensible power kW
Input temp. TS in indoor coil
Input temp. TS in indoor coil
Input temp. TS in indoor coil
30
27
24
22
30
27
24
22
30
27
24
22
(Mini‐
mum)
9500
23
68.8
14.6
41.3
32.5
23.8
-
65.3
16
40
31.3
22.5
-
58.8
17.7
38
29.2
20.5
-
19
62.3
14.2
54.5
45.7
36.9
31.1
58.8
15.4
53
44.3
35.5
29.7
52.9
16.6
50.1
42.1
33.3
27.5
17
58.8
13.9
58.8
52.1
43.3
43.7
54.1
15.2
54.1
49.8
41.1
38.7
48.2
16.5
48.2
47.5
38.8
32.9
15
52.9
13.7
52.9
52.9
48.2
42.3
50.6
14.9
50.6
50.6
46.9
41.1
45.3
16.3
45.3
45.3
44.7
38.9
(Nominal)
11500
23
71.4
14.9
45.4
35
24.7
-
67.7
16.3
44.2
33.8
23.4
-
61
18.1
42.1
31.7
21.3
-
19
64.6
14.4
60.8
50.5
40.1
33.1
61*
15.7*
59.4
49*
38.6
31.7
54.9
17
54.9
45.8
36.4
29.5
Installation manual
1
ARC/ARG Performance 1.11