Flow
m
3
/h
Return
air TS
ºC
Outdoor air temperature TS ºC
-10
-5
0
5
7
10
15
20
PT
PC
PT
PC
PT
PC
PT
PC
PT
PC
PT
PC
PT
PC
PT
PC
25
47
18.2
53.1
19
60.1
19.8
67.8
20.3
71
21.2
76.2
22
85.4
23.5
95.2
24.4
*
Data in accordance with Eurovent Rooftop program certification conditions
PT: Total Power; PC: Power absorbed by the compressor
WB: Wet-bulb temperature; TS: Dry bulb temperature.
1.12.8 ARH/ARD 090 Thermodynamic heat capacity
Flow
m
3
/h
Return
air TS
ºC
Outdoor air temperature TS ºC
-10
-5
0
5
7
10
15
20
PT
PC
PT
PC
PT
PC
PT
PC
PT
PC
PT
PC
PT
PC
PT
PC
(Minimum)
13000
14
57.7
18.4
65.2
19.2
73.9
20
83.3
20.5
87.3
21.4
93.6
22.2
105
23.8
117
24.6
17
57.1
20
64.5
20.8
73
21.7
82.3
22.2
86.3
23.2
92.5
24
103.7
25.8
115.7
27
20
56.4
20.4
63.7
21.2
72.1
22.2
81.4
22.7
85.3
23.7
91.4
24.6
102.5
26.3
114.3
27.3
23
55.6
21.8
62.9
22.7
71.2
23.7
80.3
24.3
84.2
25.4
90.2
26.3
101.2
28.2
112.8
29.2
25
55.3
22.5
62.5
23.4
70.8
24.4
79.8
24.9
83.7
26.1
89.7
27
100.6
29
112.1
30
(Nominal)
16000
14
58.5
17.9
66.2
18.6
74.9
19.4
84.5
19.8
88.6
20.8
95
21.5
106.5
23
118.7
23.9
17
57.9
19.3
65.4
20.1
74
21
83.5
21.5
87.5
22.5
93.8
23.3
105.2
25
117.3
25.9
20
57.2
19.8
64.6
20.6
73.2
21.5
82.5
22
86.5*
23*
92.7
23.8
104
25.5
116
26.4
23
56.4
21.2
63.8
22
72.2
23
81.4
23.5
85.4
24.6
91.5
25.5
102.6
27.3
114.4
28.3
25
56.1
21.8
63.4
22.6
71.8
23.7
81
24.2
84.9
25.3
91
26.2
102
28.1
113.7
29.1
(Maximum)
18000
14
59.1
17.4
66.8
18.1
75.7
18.9
85.3
19.3
89.5
20.2
96
20.9
107.5
22.4
119.9
23.3
17
58.4
18.8
66
19.6
74.8
20.5
88.4
20.9
88.4
21.9
94.8
22.7
106.3
24.3
118.5
25.2
20
57.7
19.3
65.3
20
73.9
20.9
83.3
21.4
87.4
22.4
93.7
23.2
105
24.8
117
25.8
23
57
20.6
64.4
21.4
73
22.4
82.3
22.9
86.2
24
92.4
24.8
103.6
26.6
115.5
27.6
25
56.7
21.2
64
22
72.5
23
81.8
23.5
85.7
24.6
91.9
25.5
103
27.3
114.8
28.3
*
Data in accordance with Eurovent Rooftop program certification conditions
PT: Total Power; PC: Power absorbed by the compressor
WB: Wet-bulb temperature; TS: Dry bulb temperature.
1.13 Indoor fan
1.13.1 Features table
Model
Fan kit
Motor (1)
Motor pulley (adjustable)
Fan pulley (fixed)
Belt
kW
Type of cas‐
ing
∅ pulley (mm)
∅ shaft
(mm)
∅ pulley
(mm)
∅ shaft
(mm)
Length (mm)
Ref.
Qty.
045
Standard
3
100 LB
109-135
28
236
25
1840
BX71
1
Option HPD 4 kW
4
100 LC
109-135
28
190
25
1740
BX67
1
060
Standard
4
100 LC
124-150
28
236
25
2040
BX79
1
Option HPD 5.5 kW
5,5
112 MB
147-178
28
236
25
2040
BX79
1
075
Standard
5,5
112 MB
124-150
28
236
25
2040
BX79
1
Option HPD 7.5 kW
7,5
132 M
147-178
38
236
25
2123
BX82
1
090
Standard
7,5
132 M
139-173
38
250
35
2040
BX79
2
Option HPD 9.2 kW
9,2
132 MBA
139-173
38
250
35
2040
BX79
2
Option HPD 11 kW
11
132 MB
152-190
38
250
35
2040
BX79
2
(1) All motors are totally closed, cooled by fans at 1450 r/min, with a solid base and a service factor of 1.15.
Inside fan output tables for determining the motor pulley adjustment and the type of drive needed for the installation.
1.13.2 Considerations when consulting the output tables
Indoor fan output tables
For units with 0% outdoor air and 100% return air, dry indoor coil, and standard G4 filters.
1
Installation manual
1.13 Indoor fan
18