Place separators -1- above the unit to prevent the ca‐
bles or slings from touching it.
Attach guide ropes so that that the unit does not rotate
freely.
The cables or slings should be long enough to form
an angle of over 45º to the horizontal plane. Hoist the
unit keeping it in a horizontal position.
D A N G E R
There should not be onlookers within a radius of 10
m of the unit when it is being hoisted.
Centre of gravity of the unit
Models
045
060
075
090
A
1180
1180
1135
1080
B
1390
1425
1480
1540
C
3180
3180
3495
3495
D
2337
2337
2337
2337
All measurements in mm.
1. Centre of gravity
2. End of the outdoor coil
1.4 Technical data
1.4.1 Technical and physical data for ARC (cool only) and ARG (cool only
+ gas heat)
Models
ARC/ARG
045
060
075
090
Cooling capacity(1)
Net cooling capacity
kW
45,1
61
71,5
84
Rated absorbed power in cool mode
kW
16
23
30
36
Heating (ARC)
Optional electric heating capacity (400
V) (2)
kW
12-25-37-50
Gas Heating (ARG)
Heat capacity at 100% power (standard)
(LHV) Total
kW
85
Net (2) kW
76
Heat capacity at 100% power, high ca‐
pacity (optional)
Total kW
100
Net (2) kW
90
100% gas consumption (2ND-H natural
gas, G20 at 20 mbar and 15ºC) (stand‐
ard)
m
3
/h
8,6
100% gas consumption (2ND-H natural
gas, G20 at 20 mbar and 15ºC) high ca‐
pacity (optional)
m
3
/h
9,8
Stages
No.
2
Compressors
Rated/start-up current
A
2x12/95
2x15/118
2x20/140
2x25/198
Type and quantity
SCROLL, 1 (TANDEM 50% + 50%)
Degree of protection
IP21
Refrigerant (R-410A)
kg
10,5
18,2
20,5
29
Electric power supply
V / ph / Hz
400/3+N/50
Indoor fan (3)
Rated air flow
m
3
/h
8500
11500
13500
16000
1
Installation manual
1.4
Technical data