2 Connect the duct system to the panel flanges.
Minimum clearance above the unit
The unit is designed to be installed outdoors.
In ground level installations, the building eaves should be at a vertical distance of at least 1830 mm from
the top of the unit and should not overhang the unit more than 915 mm.
There are no restrictions regarding the overhang if the eaves are 3000 mm or more above the unit.
1.10.2 General dimensions and ac‐
cesses (models 045/060)
A. Combustion exhaust hood
B. Combustion air input hood
C. Access to gas heating system
D. Gas supply intake (∅ 58 mm), with rubber grommet
E. RAG/RAD unit details
F. Access to motor, fan and pulleys
G. Access to heating options
H. Access to control system
I.
Control cable intake (∅ 23 mm) (side)
J. Power cable intake (∅ 38 + 29 mm) (side)
K. Opening for connection of lower supply and return air ducts.
L. Control cable intake (PG 21 mm) (lower)
M. Power cable intake (PG 48 mm) (lower)
Installation manual
1
Measurements, clearances and accesses 1.10
11