Return air
Outdoor coil air temperature (TS)
Flow
m
3
/h
TH
ºC
27 ºC
35 ºC
46 ºC
PT
kW
PC
kW
Sensible power kW
PT
kW
PC
kW
Sensible power kW
PT
kW
PC
kW
Sensible power kW
Input temp. TS in indoor coil
Input temp. TS in indoor coil
Input temp. TS in indoor coil
30
27
24
22
30
27
24
22
30
27
24
22
17
61
14.1
61
58
47.6
49.8
56.1
15.5
56.1
55.7
45.3
43
50
16.8
50
50
43
36.1
15
54.9
14
54.9
54.9
53.5
46.6
52.5
15.2
52.5
52.5
52.3
45.3
47
16.6
47
47
47
43.1
(Maxi‐
mum)
13500
23
73.2
15.1
49.3
37.3
25.4
-
69.5
16.5
48.1
36.1
24.1
-
62.6
18.3
46
34
22.1
-
19
66.4
14.6
66.4
55
43
35
62.6
15.9
62.6
53.5
41.6
33.6
56.3
17.2
56.3
51.4
39.4
31.4
17
62.6
14.3
62.6
62.6
51.6
56
57.8
15.7
57.8
57.6
49.4
47.2
51.3
17
51.3
51.3
47
39
15
56.3
14.2
56.3
56.3
56.3
50.7
53.8
15.4
53.8
53.8
53.8
49.4
48.2
16.9
48.2
48.2
48.2
47.2
*
Data in accordance with Eurovent Rooftop program certification conditions
PT: Total Power; PC: Power absorbed by the compressor
WB: Wet-bulb temperature; TS: Dry bulb temperature.
1.11.3 ARC/ARG 075 Cooling capacities
Return air
Outdoor coil air temperature (TS)
Flow
m
3
/h
TH
ºC
27 ºC
35 ºC
46 ºC
PT
kW
PC
kW
Sensible power kW
PT
kW
PC
kW
Sensible power kW
PT
kW
PC
kW
Sensible power kW
Input temp. TS in indoor coil
Input temp. TS in indoor coil
Input temp. TS in indoor coil
30
27
24
22
30
27
24
22
30
27
24
22
(Mini‐
mum)
11500
23
81.2
19.5
49.3
38.7
28
-
77
21.3
47.8
37.2
26.6
-
69.4
23.6
45.4
34.8
24.2
-
19
73.6
18.9
65.2
54.6
44
36.9
69.4
20.5
63.5
52.9
42.3
35.2
62.5
22.1
61
50.4
39.7
32.7
17
69.4
18.5
69.4
62.6
51.7
52
63.8
20.3
63.8
59.8
49.1
46
56.9
21.9
56.9
56.9
46.4
39.3
15
62.5
18.2
62.5
62.5
57.6
50.6
59.7
19.9
59.7
59.7
56.1
49.1
53.4
21.7
53.4
53.4
53.4
46.5
(Nominal)
13500
23
83.7
19.9
53.4
41.1
28.9
-
79.4
21.7
51.9
39.7
27.4
-
71.5
24
49.5
37.3
25
-
19
75.8
19.2
71.6
59.3
47.1
38.9
71.5*
20.9*
70
57.7*
45.4
37.2
64.3
22.6
64.3
55.1
42.8
34.7
17
71.5
18.8
71.5
68.2
56
58.1
65.8
20.7
65.8
65.6
53.3
50.3
58.6
22.4
58.6
58.6
50.6
42.4
15
64.3
18.6
64.3
64.3
63
54.9
61.5
20.3
61.5
61.5
61.5
53.4
55
22.2
55
55
55
50.8
(Maxi‐
mum)
16000
23
86
20.1
58.3
44.1
29.8
-
81.6
22
56.9
42.6
28.3
-
73.5
24.4
63.2
40.2
25.9
-
19
78
19.5
78
65
50.8
41.3
73.5
21.2
73.5
63.3
49.1
39.6
66.2
22.9
54.4
60.8
46.5
37
17
73.5
19.1
73.5
73.5
61
65.6
67.6
21
67.6
67.6
58.4
55.5
60.3
22.7
66.2
60.3
55.6
46.1
15
66.2
18.9
66.2
66.2
66.2
60
63.2
20.6
63.2
63.2
63.2
58.5
56.6
22.5
60.3
56.6
56.6
55.8
*
Data in accordance with Eurovent Rooftop program certification conditions
PT: Total Power; PC: Power absorbed by the compressor
WB: Wet-bulb temperature; TS: Dry bulb temperature.
1.11.4 ARC/ARG 090 Cooling capacities
Return air
Outdoor coil air temperature (TS)
Flow
m
3
/h
TH
ºC
27 ºC
35 ºC
46 ºC
PT
kW
PC
kW
Sensible power kW
PT
kW
PC
kW
Sensible power kW
PT
kW
PC
kW
Sensible power kW
Input temp. TS in indoor coil
Input temp. TS in indoor coil
Input temp. TS in indoor coil
30
27
24
22
30
27
24
22
30
27
24
22
(Mini‐
mum)
13000
23
94.5
19.5
57.8
45.2
32.6
-
89.7
21.3
56.2
43.6
31
-
80.8
23.6
53.4
40.8
28.2
-
19
85.6
18.9
76.7
64.1
51.5
43.1
80.8
20.5
74.8
62.2
49.6
41.1
72.7
22.1
71.8
59.2
46.6
38.2
17
80.8
18.5
80.8
73.3
60.7
56.2
74.3
20.3
74.3
70.3
57.7
51.4
66.3
21.9
66.3
66.3
54.5
46.1
15
72.7
18.2
72.7
72.7
67.8
59.4
69.5
19.9
69.5
69.5
66.1
57.7
62.2
21.7
62.2
62.2
62.2
54.7
(Nominal)
16000
23
98.2
22.8
64.6
49.3
34
-
93.2
25
62.9
47.6
32.3
-
84
27.6
60.1
44.8
29.5
-
19
89
22.1
87.3
71.9
56.6
46.4
84*
24*
84
70*
54.7
44.5
75.6
25.9
75.6
67
51.7
41.5
17
84
21.6
84
83
67.7
63.8
77.3
23.8
77.3
77.3
64.6
57.5
68.9
25.7
68.9
68.9
61.4
51.2
15
75.6
21.4
75.6
75.6
75.6
66.4
72.2
23.3
72.2
72.2
72.2
64.7
64.7
25.4
64.7
64.7
64.7
61.7
(Maxi‐
mum)
18000
23
100
23.1
68.9
51.8
34.7
-
95
25.3
67.3
50.2
33.1
-
85.6
27.9
64.5
47.4
30.3
-
19
90.7
22.4
90.7
77
60
48.5
85.6
24.3
85.6
75
57.9
46.5
77
26.2
77
72
54.9
43.5
17
85.6
21.9
85.6
85.6
72.2
68.9
78.8
24.1
78.8
78.7
69.1
61.4
70.2
26
70.2
70.2
65.9
54.5
15
77
21.6
77
77
77
71
73.6
23.6
73.6
73.6
73.6
69.2
66
25.8
66
66
66
66
1
Installation manual
1.11 ARC/ARG Performance
14
Summary of Contents for ARC 045
Page 1: ...ACTIVA SERIES ROOF TOP Air Conditioners Installation manual Ref N 40XXX...
Page 2: ......
Page 5: ...1 Installation manual...
Page 46: ......
Page 47: ...2 Unit installation data...
Page 52: ......