Models
ARC/ARG
045
060
075
090
Maximum static pressure with rated flow
(standard)
Pa
182
270
240
368
Maximum static pressure with rated flow
(optional HPD drive)
Pa
368
430
>500
>500
Maximum flow
m
3
/h
10000
13500
16000
18000
Minimum flow
m
3
/h
7000
9500
11500
13000
IP55 Motor (standard)
kW
3
4
5,5
7,5
Rated current
A
5,5
5,7
7,6
11,7
IP55 Motor (HPD optional)
kW
4
5,5
7,5
9,2/11
Rated current
A
5,7
7,6
11,7
14/17,4
Indoor coil (evaporator)
Number of elements
No.
2
3
3
4
Distance between fins
mm
1,81
1,81
1,81
1,81
Front surface
m
2
1,44
1,58
1,95
1,06 (x 2)
Air filters (G4)
Quantity per unit
No.
6
6
Dimensions
mm
470x550x48
565x594x48
Outdoor fan
Diameter / number
mm
800/1
800/2
800/2
800/2
Total rated flow
m
3
/h
15000
23000
27000
27000
Motor (IP54)
kW
1,9
1,9
1,9
1,9
Rated current
A
3,5
2x3,5
2x3,5
2x3,5
Outdoor coil (condens‐
er)
Number of elements
No.
2
3
2
3
Distance between fins
mm
1,81
1,81
1,81
1,81
Front area
m
2
2,27
2,49
2.31 (x2)
2.31 (x2)
Net dimensions (4)
Height
mm
1316
1367
Length
mm
3180
3495
Width
mm
2337
2337
Net weight (basic unit
without accessories) (4)
ARC
kg
900
945
1118
1142
ARG
kg
1010
1055
1228
1252
Electrical features of
the unit
Total rated power
kW
16
23
30
36
Total rated current
A
32
42
54
70
Total maximum power
kW
23
31
38
45
Total maximum current
A
42
56
70
83
Circuit breaker (K Curve (5)
A
50
63
80
100
Minimum cable section (6)
mm
2
10
16
25
35
(1) Data comply with Eurovent conditions, summer: indoor 27 °C TS / 19 °C TH - outdoor TS 35 °C (TS Dry-bulb Thermometer; TH Wet-bulb thermometer).
(2) Add the inside motor consumption to find the total calorific capacity.
(3) See
Indoor fan
, see on page 18 .
(4) Consider the additional weight of options and accessories. To do so, see
Weight options and accessories
, see on page 7 .
LHV: Lower heating value.
(5) and (6) Circuit breaker with K curve, according to DIN, VDE 0660-104. Section of cables for the power supply line based on copper conductors, 105 ºC. The indicated
circuit breaker and the section of power supply cables are guidelines. They should be adjusted based on the requirements of each installation, distance between units, fall
in planned voltage and on the application of the current regulations with respect to the country where the unit is being installed.
1.4.2 ARH technical and physical data (heat pump) and ARD (heat pump
+ gas heat)
Models
ARH/ARD
045
060
075
090
Cooling capacity(1)
Net cooling capacity
kW
47,6
61,9
71,4
83,4
Rated absorbed power in cool
mode
kW
17
20
28
36
Heat capacity
Heating capacity (2)
kW
45,2
58
71,7
86,5
Rated power absorbed in heat
mode
kW
16
19
27
33
Optional electric heating ca‐
pacity (400 V) (ARH) (2)
kW
12-25-37-50
Gas Heating (ARG)
Heat capacity at 100% power
(standard)
(LHV) Total kW
85
Net (2) kW
76
Heat capacity at 100% power,
high capacity (optional)
Total kW
100
Installation manual
1
Technical data
1.4
5