<9. Parameter Summary>
9-1
IM 01W07D01-01EN
9. Parameter Summary
Table 9.1
Parameter Summary
Object
ID
Attribute
ID
Label
Description
Default value Handling
(*
1
)
1. UAPMO
1
Version Revision Indicates the application revision of WN100. This
revision changes when the application software is
downloaded.
---
R
64
Identification
Number
Indicates the vendor ID, model ID, and revision of
the device.
---
R
67
Diagnostic
Status
Indicates the diagnostic results of the device based
on the NAMUR NE107 model.
Setting Enable diagnostic status configuration in
UAP Option to Enable allows turning OFF and
ON the display of the diagnostic results for each
summary, and changing Categorize.
---
R
68
UAP Option
Allows setting the Diagnostic Status.
0x0000: Disable diagnostic status
configuration(default)
0x8000: Enable diagnostic status configuration
Disable
diagnostic
status
configuration
W
69
Diagnostic
Switch
Allows setting On/Off for each summary of
Diagnostic Status when Enable diagnostic status
configuration in UAP Option is set to Enable.
On
W
70
Diagnostic
Configuration
Allows Categorize for each summary of Diagnostic
Status when Enable diagnostic status configuration
in UAP Option is set to Enable.
0x08: F:Failure status
0x04: C:Function check status
0x02: O:Out of specification status
0x01: M:Maintenance required status
Refer to Table
7.5.
R
102
Diagnostic
Status Detail
Detailed information on Diagnostic Status.
Refer to Table
9.2
R
103
Energy Left
Indicates the number of days of remaining battery
life assuming ambient temperature condition as 23
degrees Celsius.
Unit: day
---
R
104
Reset Energy
Left
Resets the remaining battery power calculation to
restore it to a remaining battery power calculation
which is based on new batteries.
0: Continue
1: Reset
0
(reading value
is always 0)
W
105
Power Supply
Status
Indicates remaining battery life and power supply of
device.
1: battery powered, greater than 75%
remaining capacity
2: battery powered, between 25% and 75%
remaining capacity
3: battery powered, less than 25% remaining
capacity
---
R
107
Power Supply
Voltage
Indicates the measured power supply voltage (V).
---
R
112
Adapter
Temperature
Indicates the temperature of the WN100.
---
R
113
Temperature
Unit
Selects the temperature unit to be indicated on
Adapter Temperature.
1000: K
1001: °C (default)
1002: °F
1003: °R
°C
W