4-21
IM 04P01B01-17E
Commands
4
p5
Hold/Not hold the relay
HOLD
Hold the relay output until an
alarm acknowledge operation
is executed
NONHOLD
Reset the relay output when
the alarm is cleared.
p6
Hold/Not hold the alarm status display
HOLD
Hold the display until an
alarm acknowledge operation
is executed
NONHOLD
Clear the display output when
the alarm is cleared.
p7
Interval for the high limit on rate-of-change
alarm (01 to 15)
p8
Interval for the low limit on rate-of-change
alarm (01 to 15)
p9
Alarm hysteresis on measurement channels
(OFF, 0.1%, 0.2%, 0.3%, 0.4%, 0.5%, 0.6%,
0.7%, 0.8%, 0.9%, or 1.0%)
p10
Alarm hysteresis on computation channels
(OFF, 0.1%, 0.2%, 0.3%, 0.4%, 0.5%, 0.6%,
0.7%, 0.8%, 0.9%, or 1.0%)
Query
XA?
Example
Enable fault diagnosis output. Disable reflash
and AND operations. Set the relay operation to
energize and hold. Set the alarm status display
to hold. Set the interval for the high limit of rate-
of-change alarm to 10, the interval for the low
limit of rate-of-change alarm to 12, the
measurement alarm hysteresis to 0.5%, and the
computation alarm hysteresis to OFF.
XA ON,OFF,NONE,ENERGIZE,HOLD,HOLD,
10,12,0.5%,OFF
Description • The interval for the high limit of rate-of-change
alarm is equal to “scan interval
×
p7” and the
interval for the low limit of rate-of-change
alarm is equal to “scan interval
×
p8.”
• Parameter p10 can be specified on models
with the computation function (/M1 option).
• For the details on the settings, see the
µ
R10000 Recorder User’s Manual or
the
µ
R20000 Recorder User’s Manual
.
XI
Sets the A/D integral time.
Syntax
XI p1
<terminator>
p1
Integration time of the A/D converter
AUTO
Automatically set in synch with
the power supply frequency.
50HZ
20 ms
60HZ
16.7 ms
100MS
100 ms (dot model)
Query
XI?
Example
Set the A/D integral time to 50 Hz.
XI 50HZ
Description • 100 ms is available only on the dot model.
• If Auto is specified when using the 24-VDC
power supply on a recorder with the 24-VDC/
AC power supply (/P1 option), the integration
time is fixed to 20 ms (50 Hz).
XB
Sets the burnout detection.
Syntax
XB p1,p2
<terminator>
p1
Channel number
p2
The procedure taken when a sensor
burnout is detected
OFF
Disable the burnout detection.
UP
Set the recording off the scale to the
right when a burnout is detected.
DOWN
Set the recording off the scale to the
left when a burnout is detected.
Query
XB[ p1]?
Example
Set the recording off the scale to the right when a
sensor burnout is detected on channel 01.
XB 01,UP
XJ
Sets the RJC.
When using the internal compensation circuit
Syntax
XJ p1,p2
<terminator>
p1
Channel number
p2
Reference junction compensation selection
(INTERNAL)
Query
XJ[ p1]?
Example
Use the internal compensation circuit on channel
01.
XJ 01,INTERNAL
When using an external RJC
Syntax
XJ p1,p2,p3
<terminator>
p1
Channel number
p2
Reference junction compensation selection
(EXTERNAL)
p3
Compensation voltage (–20000 to 20000)
[
µ
V]
Query
XJ[ p1]?
Example
Set the reference junction compensation of
channel 02 to external and set the compensation
voltage to 0
µ
V.
XJ 02,EXTERNAL,0
Description The unit of p3 is
µ
V (microvolts).
UC
Changes the dot color (dot model).
Syntax
UC p1,p2
<terminator>
p1
Channel number
p2
Dot color
PURPLE
RED
GREEN
BLUE
BROWN
BLACK
Query
UC[ p1]?
4.5 Basic Setting Commands