4-22
IM 04P01B01-17E
Example
Set the dot color of channel 06 to purple.
UC 06,PURPLE
Description On models with the computation function (/M1
option), the dot color of computation channels
can be changed.
UO
Sets the pen offset
compensation (pen model).
Syntax
UO p1
<terminator>
p1
Pen offset compensation ON/OFF (ON, OFF)
Query
UO?
Example
Use the pen offset compensation.
UO ON
UP
Sets the items to be printed.
Pen model
Syntax
UP p1,p2,p3,p4,p5,p6
<terminator>
p1
Channel number/tag selection
CHANNEL
Print the channel number
TAG
Print the tag
p2
Alarm printout
ON1
Print at alarm occurrence and release
ON2
Print at alarm occurrence
OFF
Do not print
p3
Record start time printout ON/OFF (ON, OFF)
p4
New chart speed printout ON/OFF (ON, OFF)
p5
Scale printout ON/OFF (ON, OFF)
p6
Recording color printout ON/OFF (ON, OFF)
Query
UP?
Example
Print tags. Print all items.
UP TAG,ON1,ON,ON,ON,ON
Dot model
Syntax
UP p1,p2,p3,p4,p5,p6
<terminator>
p1
Channel number/tag selection
CHANNEL
Print the channel number
TAG
Print the tag
p2
Channel number printout ON/OFF (ON,
OFF) by the trend recording
p3
Alarm printout
ON1
Print at alarm occurrence and release
ON2
Print at alarm occurrence
OFF
Do not print
p4
Record start time printout ON/OFF (ON, OFF)
p5
New chart speed printout ON/OFF (ON, OFF)
p6
Scale printout ON/OFF (ON, OFF)
Query
UP?
Example
Print the channel numbers. Print all items.
UP CHANNEL,ON,ON1,ON,ON,ON
UR
Sets the periodic printout interval.
Syntax
UR p1,p2,p3,p4
<terminator>
p1
Print interval mode
Auto
Automatically set the interval
according to the chart speed
Manual
Specify the interval
p2
Reference time (00 to 23 [hour])
p3
Interval (10min, 12min, 15min, 20min,
30min, 1h, 2h, 3h, 4h, 6h, 8h, 12h, 24h)
(when p1 is Manual)
p4
Periodic printout mode
OFF
Disable periodic printout
INST
Print instantaneous values.
REPORT
Print the report data over the
interval.
Query
UR?
Example
Carry out periodic printout every 2 hours with
hour 0 as the reference. Print the measured
values (instantaneous values) at each interval.
UR Manual,00,2h,INST
Description • When p1 is set to Auto, the periodic printout
interval synchronizes to the chart speed.
• If p4 is set to REPORT, set the type of report
data on each channel using the UM command.
UM
Sets the types of report data that
are output to the periodic
printout.
Syntax
UM p1,p2,p3
<terminator>
p1
Channel number
p2
Type of report data
INST
Instantaneous value
AVE
Average value
MIN
Minimum value
MAX
Maximum value
SUM
Sum value
MIX
A m
maximum values
p3
Sum scale
OFF
Integrates the data per scan
interval.
/s
Integrates the physical amount
that are in unit of /s.
/min
Integrates the physical amount
that are in unit of /min.
/h
Integrates the physical amount
that are in unit of /hour.
/day
Integrates the physical amount
that are in unit of /day.
Query
UM[ p1]?
Example
Print the average values of channel 03 using
periodic printout.
UM 03,AVE
Description • This setting is possible when printing of report
data (p4 is REPORT) is specified using the
UR command.
• About p3
The data for sum computation are sampled
every scan interval. For data with units such
as /s, /min, /h, and /day as in a flow rate, the
data can be summed over the unit time.
Parameter p3 is valid only for sum values.
4.5 Basic Setting Commands