3-14
IM 04P01B01-17E
3.5
Setting the Serial Interface
The serial interface must be configured.
Setup Items
RS422/485
Address
End
Baud rate
Data length
Parity
Protocol
Procedure
For a description of the basic operations, see “Basic Key Operations” on page vi.
Entering Basic Setting Mode
Hold down the
MENU
key for 3 seconds to display the Setting mode screen.
Next, hold down both the
(
DISP
) key and the
(
FUNC
) key for 3 seconds to
display the Basic Setting mode screen.
Note
To cancel an operation, press the
ESC
key.
1.
Press the
key to select
RS422/485
and then press the
key.
Basic=RS422/485
2.
Press the
key to select the recorder’s address and then press the
key.
Address=1
3.
Press the
key to select the
Baud rate
value and then press the
key.
Baud rate=38400
4
Press the
key to select the
Data length
value and then press the
key.
Data length=8
5
Press the
key to select the
Parity
value and then press the
key.
Parity=Even
6.
Press the
key to select the
NORMAL
or
MODBUS
value and then press
the
key.
The setting complete screen appears.
Protocol=NORMAL
RS422/485
Setting complete
Saving the Settings
1.
Press the
ESC
key to return to the
Basic=
screen.
2.
Press the
key to select
End
and then press the
key.
3.
Press the
key to select
Store
and then press the
key.
The settings are activated, and the Operation mode screen appears.
* When the key or key is pressed while holding down the
SHIFT
key, the operation is
reversed as when the respective key is pressed by itself.