<10. Parameter Summary>
10-9
IM 01C27B01-01EN
Object
ID
Attribute
ID
Label
Description
Default
value
Handling
7.
AI3
block
(continued)
2
Block Mode
A universal parameter to indicate the block’s operation
status. O/S, Auto, and Man can be selected.
1. Target : Specify Al object mode.
2. Actual : Indicates current mode of Al object.
3. Permitted : Indicates the mode selected by Target
of Al object.
4. Normal : Indicate normal status mode of Al object.
1. Target =
Auto
2. Actual =
Auto
3. Permitted =
O/S+Auto
+Man
4. Normal =
Auto
W
3
Concentrator OID
Indicates the Concentrator object value that
corresponds to the data update of the PV value.
3
R
4
Scale
Allows specifying the upper or lower limit for the PV
scaling, unit code, etc.
1. EU at 100% : Indicate the upper limit of the PV
value.
2. EU at 0% : Indicate the lower limit of the PV value.
3. Units Index : Indicate the setting unit used for the
PV value.
4. Decimal : Indicate the digit number below the
decimal point displayed in the LCD indicator.
1. EU at 100%
= 100
2. EU at 0%
= 0
3. Units Index
= %
4. Decimal = 2
W
26
Tag Description
A universal parameter to store the comment that
describes the tag
AI3: Capsule
temperature
W
27
Process Value
Filter Time
Allows adjusting the time constant for filtering the PV
value.
Setting unit: Second. This is enabled for the
Continuous mode.
0 second
W
28
Simulate Switch
A simulation function switch for the AI object test
(Disable, Enable)
Disable
W
29
Transducer Value
When Simulate Switch is set to Disable, this value is
used as the input value for the AI object.
---
R
30
Simulate Value
When Simulate Switch is set to Enable, this value is
used as the input value for the AI object.
The input value can be changed.
---
W
53
Sensor Range
Parameter to nondimensionalize the sensor output
value.
K and deg C are selectable for the temperature unit.
1. EU at 100% : Indicates input value of the upper
limit.
2. EU at 0% : Indicates input value of the lower limit.
3. Units Index : Indicates the units of the
measurement range.
4. Decimal : Indicates the digit number below the
decimal point.
1. EU at 100%
= 130
2. EU at 0%
= -50
3. Units Index
= deg C
4. Decimal = 0
W
102
Tertiary Value
Select
Specifies either the capsule temperature or amplifier
temperature as the output value.
(CAP, AMP)
CAP
W
(Note) Handling: R=Read only, W=Read & Write
(Note) “Factory NAMU
R
category” refers to the four categories (C: Check function, M: Maintenance required, F: Failure, and O: Off
specification) according to NAMUR NE107*.
*1:
NAMUR NE107 “Self-Monitoring and Diagnosis of Field Devices”
*2: It is valid for not only continuous mode but also intermittent mode.