<10. Parameter Summary>
10-2
IM 01C27B01-01EN
Object
ID
Attribute
ID
Label
Description
Default
value
Handling
1.
UAPMO
block
(continued)
105
Power Supply
Status
Indicates the predicted battery level and the power
supply method.
0 = external power supply
1 = battery level 75% or more
2 = battery level 25% ~ 75%
3 = battery level 25% or less
R
106
EHType
Available to write note into this parameter.
---
W
107
Power Supply
Voltage
Indicates the measured power supply voltage (V).
---
R
110
Hardware Write
Protect
Allows recognizing the status of the hardware write
protection switch.
(Switch Off, Switch On)
R
111
Radio Silence
Repeats a cycle of a 1-hour pause and 6-minute
search if the instrument cannot join the network after a
time specified in Radio Silence has elapsed.
When 0 is set, the Radio Silence is invalid.
28800
W
112
Simulation Active
Alert
The On/Off or priority for Simulation Active Alert can
be set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
1. TRUE
2. 15
W
113
Soft Update
incomplete Alert
The On/Off or priority for Soft Update incomplete Alert
can be set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
Not available for EJX.
1. TRUE
2. 15
W
114
Power low Alert
The On/Off or priority for Power low Alert can be set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
1. TRUE
2. 15
W
115
Power Critical low
Alert
The On/Off or priority for Power Critical low Alert can
be set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
1. TRUE
2. 15
W
116
Fault prediction
Alert
The On/Off or priority for Fault prediction Alert can be
set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
Not available for EJX.
1. TRUE
2. 15
W
117
Environmental
conditions Alert
The On/Off or priority for Environmental conditions
Alert can be set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
1. TRUE
2. 15
W
118
Outside sensor
limits Alert
The On/Off or priority for Outside sensor limits Alert
can be set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
1. TRUE
2. 15
W
119
Out of service Alert The On/Off or priority for Out of service Alert can be
set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
1. TRUE
2. 15
W
120
Callibration
problem Alert
The On/Off or priority for callibration problem Alert can
be set.
1. On/Off setting
0 = FALSE, 255 =TRUE
2. Alert report priority: 0 to 15
1. TRUE
2. 15
W