<10. Parameter Summary>
10-4
IM 01C27B01-01EN
Object
ID
Attribute
ID
Label
Description
Default
value
Handling
3.
CO
block
(continued)
4
PUB_ITEM_MAX
Maximum PUB_ITEM value
---
R
5
PUB_ITEM_NUM
PUB_ITEM number
---
R
6
PUB_ITEM
Indicates the PUB_ITEM information. The following
shows the components
1. ObjectID
2. AttributeID
3. AttributeIndex
4. Size
---
W
4.
TRANSDUCER
block
1
Tag Description
Memo field available to write anything.
Transducer
W
2
Auto Recovery
Allows specifying the action when the cause of a
sensor failure is removed.
OFF (=0):
AL continues to be indicated
even after the cause of the sensor
error is removed, and the BURN
OUT state is not released.
ON (=1):
The AL indication for sensor
failure disappears and normal
action is resumed when the cause
of the sensor failure is removed.
ON
W
3
Model
Indicates the model name of the transmitter.
---
R
4
Sensor Serial
Number
Indicates the device number of the transmitter.
---
R
6
Measurement
Mode
Measurement mode selects continuous mode or
intermittent mode.
When the update time is set to 0.5 second in
intermittent mode, the mode is automatically switched
to continuous mode.
When the update time is set to 0.5 second, the
computation process is in continuous mode,
regardless of the measurement mode.
When 0 is set, measurement period is set to 30
seconds regardless of measurement setting.
intermittent
mode
W
7
Wireless Status
Indicate the communication status.
1. Indicates the initial idle status or join status.
(idle status, join status)
2. Indicates whether Contract(Pub) is established.
(not establishment, establishment)
3. Indicates whether Contract(R/W) is
established.
(not establishment, establishment)
1. idle status
2. not
estabilishment
3. not
esabilishment
R
8
Display Selection
Select PV Value displaying on the LCD indicator.
1. Indicates display status of PV Value of AI1
(displayed, not displayed)
2. Indicates display status of PV Value of AI2
(displayed, not displayed)
3. Indicates display status of PV Value of AI3
(displayed, not displayed)
1. displayed
2. not
displayed
3. not
displayed
W
9
LCD Mode
Select the display mode on the LCD indicator.
1. Indicates the ON mode. (OFF, ON)
2. Indicates the bar graph display.
(bar graph not displayed, bar graph displayed)
1. OFF
2. bar graph
not displayed
W
10
Special Cmd
Special function parameter.
0 = initialize value at READ (None)
1 = Squawk status
2 = deep sleep status
To start from deep sleep mode, either remove and
insert the battery pack, or use the provisioning device
tool or the device configuration tool via infrared
communication.
0
W