<10. Parameter Summary>
10-8
IM 01C27B01-01EN
Object
ID
Attribute
ID
Label
Description
Default
value
Handling
6.
AI2
block
(continued)
53
PV Range
Sets the measurement range.
1. EU at 100% : Indicates input value of the upper
limit.
2. EU at 0% : Indicates input value of the lower limit.
3. Units Index : Indicates the units of the
measurement range.
4. Decimal : Indicates the digit number below the
decimal point.
1. EU at
100% =
25000.000000
EU at 0%
= 0
Units Index
= kPa
Decimal
= 2
W
54
Linearization Type
Select either No Linearization or Square root as a
setting of the output range.
0 = No Linearization :
Provides an output value scaled according to the
PV Range and Scale range settings.
(To use Direct with FF, set the same value for PV
Range and Scale.)
0
W
55
Flow Constant
Indicates the flow coefficient, which shows the
correlation between the flow rate value and square root
value of the pressure.
1.0
W
56
Lower Cutoff
Specifies the low cut value. The unit is subject to
Scale.Units Index.
10
W
57
Cal Cmd
Specifies the calibration method.
0 = CAL_NONE : Initial state in which calibration is
not performed
1 = CAL_LOW : Applies an actual input and adjusts
the lower limit using the value specified in
Calibration Lowest Point.
2 = CAL_HIGH : Applies an actual input and adjusts
the higher limit using the value specified in
Calibration Highest Point.
5 = CAL_CLEAR : Clears the adjustment variable.
0 (reading
value is
always 0)
W
58
Cal Status
Indicates the calibration status.
0 = CAL_NONE : Start-up and default value
1 = CAL_SUCCESS : Indicates that calibration was
successful.
7 = CAL_BAD_TRIM_POINT : Indicates this status
when the adjustment variable is outside of range.
R
59
Calibration Highest
Point
Specifies the higher limit adjustment variable for
adjustment between two points.
---
W
60
Calibration Lowest
Point
Specifies the lower limit adjustment variable for the
adjustment between two points.
---
W
61
Calibration
Minimum Span
Indicates the minimum span of the adjustment
variable.
108 = Gauge pressure
109 = Absolute pressure
---
R
102
Static Process
Type
Selects the gauge pressure or the absolute pressure.
Abs
W
103
SP Select
Parameter to select the High-side pressure or the Low-
side pressure as the static pressure output.
0 = High : Displays the H-side pressure as the static
pressure
1 = Low : Displays the L-side pressure as the static
pressure
High
W
7.
AI3
block
1
Process Value
Al3 is a temperature pressure output object.
Indicates the primary analog value (or corresponding
process value) and status used to execute this
function.
Allows updating data by specifying this for the
Concentrator object.
1. Value: output value of Al object
2. Status: Specify output status of Al object.
1. Value = ---
2. Status = ---
W