YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World!
YMGI: Your Modern Green Idea
82
Removal of condenser
NOTE:
Before removing the condenser, make sure there is no refrigerant in the pipeline and power is cut off.
Step
Picture
Work instruction
1. Remove the panels.
Remove the upper, lower and
front panels.
2. Remove the electric box.
Loosen the wire clamp at the
bottom of the electric box.
Unscrew the screws of electric
box.
The connection wires inside and
outside the electric box should be
removed.
3. Remove motor support.
When removing the motor
support, be careful to protect the
components.
4. Remove the condenser.
Heat up the welding points of
connection pipes through gas
welding until the pipes break off.
NOTE
: When welding the pipes,
do not let the flame burn the other
components. The welding points
of condenser are steel and
copper welding points. Be sure to
maintain the welding quality.