“F6” ODU Tube Temperature Sensor Error
Error display:
ODU mainboard LED displayer
Error judgment condition and method:
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge the range of AD
value. If the sampling AD value exceeds upper limit and lower limit in 5 seconds continuously, report the error.
Possible reason:
Poor contact between temperature sensor and terminal in mainboard interface
Temperature sensor is abnormal
Detecting circuit is abnormal
Troubleshooting
:
NOTE:
Please refer to Appendix 1 for the relation between temperature and resistance of temperature sensor.