“E4” Compressor Air Discharge High-temperature Protection
Error display:
ODU mainboard LED displayer
Error judgment condition and method:
Test the compressor discharge temperature through compressor discharge pipe and shell top temperature sensor. If the
tested temperature value is higher than 115
℃
, the unit will stop for protection
Possible reason
:
Cut-off valve of ODU is not fully opened
Electronic expansion valve is abnormal
Outdoor or indoor fan is not working properly
IDU filter or air duct is blocked (cooling mode)
Ambient temperature exceeds allowable operation range
Refrigerant charging amount is insufficient
System pipeline is blocked
Troubleshooting: