YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World!
YMGI: Your Modern Green Idea
43
“H5” IPM Protection
Error display:
ODU mainboard LED displayer
Error judgment condition and method:
When power is connected and drive chip received IPM lead F0 that is of low level, than it is IPM module malfunction.
System will shut down for protection.
Possible reason:
Compressor 3-phase wire connection is lack of phase or phase-reversed.
System is overloaded and compressor current is too large.
Drive board IPM module is damaged.
Drive board IPM module’s 15V power supply is lower than 13.5V.
Drive board 6-line PWM signal and the corresponding element are abnormal.
Drive board compressor current sampling circuit element is damaged or drive chip current sampling AD terminal
is abnormal.
Compressor is damaged.
Troubleshooting
: