YMGI, Engineered Comfort Products for A Sustainable and Efficient Green World!
YMGI: Your Modern Green Idea
54
“PH” Bus High-Voltage Protection
Error display:
ODU mainboard LED displayer
Error judgment condition and method:
If there is no other malfunction and the busbar voltage is higher than the set value for high voltage protection, then it can
be judged that bus high-voltage protection occurs. System will shut down for protection.
Possible reason:
Voltage of power grid is abnormal.
Drive board busbar voltage sampling circuit element is damaged or driveboard busbar voltage sampling AD
terminal is abnormal.
Troubleshooting
:
“PU” Charge Loop Error
Error display:
ODU mainboard LED displayer
Error judgment condition and method:
When the charge loop starts to get charged and the busbar voltage cannot reach the set value in a certain period of time,
then it can be judged that charge loop error exists. System will shut down for protection.
Possible reason:
Voltage of power grid is abnormal. Voltage is too low.
Drive board charge loop element is abnormal.
Drive board busbar voltage sampling circuit element is damaged or drivechip busbar voltage sampling AD
terminal is abnormal.
Troubleshooting
: