Register No.
Contents
000FH
Control Selection Setting
bit 0
Reserved
bit 1
PI Setpoint Input
bit 2, bit 3
Reserved
bit 4
PI2 Target Input (enables the setting from MEMOBUS/Modbus)
bit 5 to B
Reserved
bit C
Enable Terminal S5 Input for Broadcast Data
bit D
Enable Terminal S6 Input for Broadcast Data
bit E
Enable Terminal S7 Input for Broadcast Data
bit F
Reserved
0010H to 001FH
Reserved
u
Monitor Data
Monitor data can be read only.
Register No.
Contents
0020H
Drive Status 1
bit 0
During Run
bit 1
During Reverse
bit 2
Drive Ready
bit 3
Fault
bit 4
Data Setting Error
bit 5
Multi-Function Contact Output 1 (terminal M1-M2)
bit 6
Multi-Function Contact Output 2 (terminal M3-M4)
bit 7
Multi-Function Contact Output 3 (terminal M5-M6)
bit 8 to D
Reserved
bit E
ComRef status
bit F
ComCtrl status
0021H
Fault Contents 1
bit 0
Overcurrent (oC), Ground fault (GF)
bit 1
Overvoltage (ov)
bit 2
Drive Overload (oL2)
bit 3
Overheat 1 (oH1), Drive Overheat Warning (oH2)
bit 4, bit 5
Reserved
bit 6
PI Feedback Loss (FbL / FbH)
bit 7
EF to EF7: External Fault
bit 8
CPF
oo
: Hardware Fault (includes oFx)
bit 9
Motor Overload (oL1), Overtorque Detection 1 (oL3), Undertorque Detection 1 (UL3)
bit A
Reserved
bit B
Main Circuit Undervoltage (Uv)
bit C
Undervoltage (Uv1), Control Power Supply Undervoltage (Uv2), Soft Charge Circuit Fault (Uv3)
bit D
Output Phase Loss (LF), Input Phase Loss (PF)
bit E
MEMOBUS/Modbus Communication Error (CE), Option Communication Error (bUS)
bit F
Operator Connection Fault (oPr)
E.9 MEMOBUS/Modbus Data Table
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
317
E
MEMOBUS/Modbus Communications
Summary of Contents for Z1000 CIMR-ZU*A Series