Table 1.25 Derated Torque Characteristics, Settings 4 to 7
Setting = 4
50 Hz
Setting = 5
50 Hz
Setting = 6
60 Hz
Setting = 7
60 Hz
0
14.4
575
1.3
25
50
100.6
V
oltage (V)
Frequency (Hz)
0
17.3
575
1.3
25
50
143.8
V
oltage (V)
Frequency (Hz)
0
14.4
575
1.5
30
60
100.6
V
oltage (V)
Frequency (Hz)
0
17.3
575
1.5
30
60
143.8
V
oltage (V)
Frequency (Hz)
Table 1.26 High Starting Torque, Settings 8 to B
Setting = 8
50 Hz
Setting = 9
50 Hz
Setting = A
60 Hz
Setting = B
60 Hz
0
20.1
575
1.3 2.5
50
43.1
V
oltage (V)
Frequency (Hz)
0
25.9
575
1.3 2.5
50
57.5
V
oltage (V)
Frequency (Hz)
0
20.1
575
1.5 3
60
43.1
V
oltage (V)
Frequency (Hz)
0
31.6
575
1.5 3
60
57.5
V
oltage (V)
Frequency (Hz)
Table 1.27 Constant Output, Settings C to F
Setting = C
90 Hz
Setting = D
120 Hz
Setting = E
180 Hz
Setting = F
60 Hz
0
17.3
34.5
575
1.5 3
90
60
V
oltage (V)
Frequency (Hz)
0
17.3
34.5
575
1.5 3
120
60
V
oltage (V)
Frequency (Hz)
0
17.3
34.5
575
1.5 3
180
60
V
oltage (V)
Frequency (Hz)
0
17.3
575
1.5
30
60
143.8
V
oltage (V)
Frequency (Hz)
Setting a Custom V/f Pattern (Setting F: Default)
Setting parameter E1-03 to F allows the user to set up a custom V/f pattern by changing parameters E1-04 to E1-13.
n
V/f Pattern Settings E1-04 to E1-13
If E1-03 is set to a preset V/f pattern (i.e., a value other than F), the user can monitor the V/f pattern in parameters E1-04
through E1-13. To create a new V/f pattern, set E1-03 to F.
Refer to V/f Pattern on page 66
for an example custom V/f
pattern.
Note:
Certain E1-
oo
parameters might not be visible depending on the control mode.
Refer to Parameter List on page 183
No.
Parameter Name
Setting Range
Default
E1-04
Maximum Output Frequency
40.0 to 240.0 Hz
E1-05
Maximum Voltage
0.0 to 733.1 V
E1-06
Base Frequency
0.0 to 240.0 Hz
E1-07
Middle Output Frequency
0.0 to 240.0 Hz
30.0 Hz
E1-08
Middle Output Frequency Voltage
0.0 to 733.1 V
143.8 V
E1-09
Minimum Output Frequency
0.0 to 240.0 Hz
E1-10
Minimum Output Frequency Voltage
0.0 to 733.1 V
E1-11
Middle Output Frequency 2
0.0 to 240.0 Hz
0.0 Hz
E1-12
Middle Output Frequency Voltage 2
0.0 to 733.1 V
E1-13
Base Voltage
0.0 to 733.1 V
0.0 V
<1> Default setting is dependent on parameter A1-02, Control Mode Selection.
<2> Default setting is dependent on parameter o2-04, Drive Model Selection.
<3> Parameter ignored when E1-11 and E1-12 are set to 0.0.
1.5 E: Motor Parameters
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
65
1
Parameter Details