n
S3-08: Secondary PI Integral Limit Setting
Sets the maximum output possible from the integrator.
No.
Name
Setting Range
Default
S3-08
Secondary PI Integral Limit Setting
0.0 to 100.0%
100.0%
n
S3-09: Secondary PI Output Upper Limit
Sets the maximum output possible from the secondary PI controller.
No.
Name
Setting Range
Default
S3-09
Secondary PI Output Upper Limit
0 to 100.0%
100.0%
n
S3-10: Secondary PI Output Lower Limit
Sets the minimum output possible from the secondary PI controller.
No.
Name
Setting Range
Default
S3-10
Secondary PI Output Lower Limit
-100.00 to 100.00
0.00%
n
S3-11: Secondary PI Output Level Selection
Sets the secondary PI controller output direction.
No.
Name
Setting Range
Default
S3-11
Secondary PI Output Level Selection
0 or 1
0
Setting 0: Normal Output (Direct Acting)
Setting 1: Reverse Output (Reverse Acting)
n
S3-12: Secondary PI Disable Mode
Selects the secondary PI controller output when disabled.
No.
Name
Setting Range
Default
S3-12
Secondary PI Disable Mode
0 to 2
0
Setting 0: No Output (0%)
Setting 1: Lower Limit (S3-10)
Setting 2: Setpoint
n
S3-13: Secondary PI Low Feedback Detection Level
Sets the secondary PI low feedback detection level.
No.
Name
Setting Range
Default
S3-13
Secondary PI Low Feedback Detection Level
0.00
<1> Upper limit is S3-02, decimal place holder is determined by S3-03.
<2> Unit is determined by S3-04.
1.11 S: Special Parameters
142
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
Summary of Contents for Z1000 CIMR-ZU*A Series
Page 339: ......