Property
Object Type
Device
Analog
Input
Analog
Output
Analog
Value
Binary
Output
Binary
Output
Binary
Value
Inactive_Text
–
–
–
–
Yes
Yes
Yes
Active_Text
–
–
–
–
Yes
Yes
Yes
<1> For Commandable Object Instances only.
u
Analog Input Objects
Table B.5 Analog Input Objects
Object ID
Object Name
Modbus
Address
Precision
Range
Units
PV Access
AI1
Analog Input 1 Level
004EH
XXXX.X
–
%
R
AI2
Analog Input 2 Level
004FH
XXXX.X
–
%
R
AI3
Not used
–
–
–
–
–
AI4
Not used
–
–
–
–
–
AI5
Not used
–
–
–
–
–
AI6
Display Format o1-03
0502H
XXXXX
–
–
R
AI7
Scale Format b5-20
01E2H
XXXXX
–
–
R
AI8
Inverter Model o2-04
0508F
XXXXX
–
–
R
AI9
Rated Current n9-01
05D0H
XXXX.X
–
Amps
R
u
Analog Output Objects
Table B.6 Analog Output Objects
Object ID
Object Name
Modbus
Address
Precision
Range
Units
PV Access
AO1
Analog Output 1 Level
0007H
XXXX.X
0 to 100.0
%
C
AO2
Analog Output 2 Level
0008H
XXXX.X
0 to 100.0
%
C
u
Analog Value Objects
Table B.7 Analog Value Objects
Object ID
Object Name
Modbus
Address
Precision
Range
Units
PV Access
AV1
Not used
–
–
–
–
–
AV2
Frequency Command
0002H
XXX.XX
Depends on
o1-03
0.00 to 600.00
Hz
Depends on
o1-03
C
AV3
PI Setpoint
0006H
XXX.XX
0.00 to 100.00
%
C
AV4
Not used
–
–
–
–
–
AV5
Not used
–
–
–
–
–
AV6
Not used
–
–
–
–
–
AV7
Not used
–
–
–
–
–
AV8
Not used
–
–
–
–
–
AV9
Frequency Reference
0040H
XXX.XX
Depends on
o1-03
–
Hz
Depends on
o1-03
R
AV10
Output Frequency
0041H
XXX.XX
Depends on
o1-03
–
Hz
Depends on
o1-03
R
AV11
Output Voltage
0045H
XXXX.X
–
Volts
R
B.7 BACnet Objects Supported