Register No.
Contents
00CCH
Alarm Contents 6
bit 0
Output Voltage Detection Fault (VoF)
bit 1
Reserved
bit 2
Capacitor Maintenance Time (LT-3)
bit 3 to C
Reserved
bit D
Motor Underload Protection (UL6)
bit E
Waiting for Run (WrUn)
bit F
Reserved
00CDH
Reserved
00CEH
Alarm Contents 7
bit 2
Time Not Set (TIM)
bit 3
Operator Battery Low (bAT)
bit 4
Time Data Error (TdE)
bit 5
External Fan Fault (Fn1)
bit 6
Emergency Override Forward Run (EoF)
bit 7
Emergency Override Reverse Run (Eor)
00CFH
Reserved
00D0H
CPF Contents 1
bit 0, 1
Reserved
bit 2
A/D Conversion Error (CPF02)
bit 3
PWM Data Fault (CPF03)
bit 4, 5
Reserved
bit 6
EEPROM Memory Data Error (CPF06)
bit 7
Terminal Board Connection Error (CPF07)
bit 8
EEPROM Serial Communications Fault (CPF08)
bit 9 to F
Reserved
00D1H
CPF Contents 2
bit 0 to 3
Reserved
bit 4
Hardware fault at power up (CPF20)
bit 5
Hardware fault at communication start up (CPF21)
bit 6
A/D Conversion Fault (CPF22)
bit 7
PWM Feedback Fault (CPF23)
bit 8
Drive Unit Signal Fault (CPF24)
bit 9 to F
Reserved
00D2H
Reserved
00D3H to 00D7H
oFA0
o
Contents (CN5)
00D8H
oFA0
o
Contents (CN5)
bit 0
Option Compatibility Error (oFA00)
bit 1
Option not properly connected (oFA01)
bit 2 to 4
Reserved
bit 5
A/D Conversion Error (oFA05)
bit 6
Option Response Error (oFA06)
bit 7 to F
Reserved
E.9 MEMOBUS/Modbus Data Table
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual