H3-01 = 0
10 V
5 V
0 V
Gain = 200 %
100 %
Frequency
reference
Bias = 0 %
E1-04
Figure 1.50 Frequency Reference Setting by Analog Input with Increased Gain
• Gain H3-03 = 100%, bias H3-04 = -25%, terminal A1 as frequency reference input:
An input of 0 Vdc will be equivalent to a -25% frequency reference.
When parameter H3-01 = 0, the frequency reference is 0% between 0 and 2 Vdc input.
0
2.0 V
10 V
100 %
Frequency
reference
-25%
H3-01 = 0
H3-01 = 1
H3-01 = 0
Analog Input
Voltage
Figure 1.51 Frequency Reference Setting by Analog Input with Negative Bias
n
H3-09: Terminal A2 Signal Level Selection
Selects the input signal level for analog input A2. Set Jumper S1 on the terminal board accordingly for a voltage input or
current input.
No.
Name
Setting Range
Default
H3-09
Terminal A2 Signal Level Selection
0 to 3
2
Setting 0: 0 to 10 V with Zero Limit
The input level is 0 to 10 Vdc. Negative input values will be limited to 0.
Refer to Setting 0: 0 to 10 V with Zero Limit on
Setting 1: 0 to 10 V without Zero Limit
The input level is 0 to 10 Vdc. Negative input values will be accepted.
Refer to Setting 1: 0 to 10 V without Zero Limit on
Setting 2: 4 to 20 mA Current Input
The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.
Setting 3: 0 to 20 mA Current Input
The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.
n
H3-10: Terminal A2 Function Selection
Determines the function assigned to analog input terminal A2.
Refer to Multi-Function Analog Input Terminal Settings on
for a list of functions and descriptions.
No.
Name
Setting Range
Default
H3-10
Terminal A2 Function Selection
0 to 26
0
1.7 H: Terminal Functions
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
93
1
Parameter Details