n
It is recommended to externally protect the electronic power supply for CPU and
backplane bus with a 3A fuse (fast) respectively by a line circuit breaker 3A character-
istics Z.
n
The power section supply of the internal I/Os is to be externally protected with a 6A
fuse (fast) respectively by a line circuit breaker 6A characteristics Z.
By means of a screwdriver there is the possibility to remove the connectors e.g. for
module exchange with a fix wiring. For this each connector has indentations for unlocking
at the top. Unlocking takes place by the following proceeding:
1.
Remove connector:
Insert your screwdriver from above into one of the indentations.
2.
Push the screwdriver backwards:
ð
The connector is unlocked and can be removed.
CAUTION!
Via wrong operation such as pressing, the screwdriver down-
ward the release lever may be damaged.
3.
Plug connector:
The connector is plugged by plugging it directly into the release lever.
2.5.2 Wiring periphery module
For wiring the periphery m module has removable connectors. With the wiring of the con-
nectors a "push-in" spring-clip technique is used. This allows a quick and easy connection
of your signal and supply lines. The clamping off takes place by means of a screwdriver.
U
max
240V AC / 30V DC
I
max
10A
Cross section
0.2 ... 1.5mm
2
(AWG 24 ... 16)
Stripping length 10mm
Use for wiring rigid wires respectively use wire sleeves. When using stranded wires you
have to press the release button with a screwdriver during the wiring.
Fusing
Remove connector
Periphery module con-
nector
Data
VIPA System MICRO
Basics and mounting
Wiring > Wiring periphery module
HB400 | CPU | M13-CCF0000 | en | 16-47