Operating parameters
Description
Assignment
Period
With the period you define the length of the output
sequence, which consists of pulse duration and pulse
pause.
Range of values:
Time base 1ms: 1 ... 87ms
Time base 0.1ms: 0.4 ... 87.0ms
20000
Minimum pulse duration
With the minimum pulse duration you can suppress short
output pulses and short pulse pauses. All pulses or
pauses, which are smaller than the minimum pulse dura-
tion, are suppressed. This allows you to filter very short
pulses (spikes), which can not be recognized by the
periphery.
Range of values:
Time base 1ms: 0 ... Period / 2 * 1ms
Time base 0.1ms: 2 ... Period / 2 * 0.1ms
2
5.8.5 Status indication
Digital output
LED
Description
DO +0.0 ... DO +0.7
green
Digital output Q+0.0 ... 0.7 has "1" signal
Digital output Q+0.0 ... 0.7 has "0" signal
DO +1.0 ... DO +1.3
green
Digital output Q+1.0 ... 1.3 has "1" signal
Digital output Q+1.0 ... 1.3 has "0" signal
Power supply
LED
Description
1L+
green
DC 24V electronic section supply
DC 24V electronic section supply not available
3L+
green
DC 24V power section supply inputs OK
DC 24V power section supply inputs not available
4L+
green
DC 24V power section supply outputs OK
DC 24V power section supply outputs not available
4M
red
Error, overload respectively short circuit on the outputs
no error