The following sensors can be connected
n
24V incremental encoders with two phase-shifted by 90° tracks
n
24V pulse encoder with direction signal
n
24V initiator as BERO or beam sensor
For not all inputs are available at the same time, for every counter you may define the
input assignment via the parameterization for the following input signals:
n
Counter
x
(A)
–
Pulse input for counter signal respectively track A of an encoder for 1-, 2- or 4-fold
evaluation.
n
Counter
x
(B)
–
Direction signal respectively track B of the encoder. Via the parameterization you
may invert the direction signal.
n
Gate 3
–
Via this input you can if parameterized open the HW gate of
Counter 3
with edge
0-1 and start counting.
n
Latch 3
–
Via this input via edge 0-1 the current counter value of
Counter 3
is stored in a
memory that you may read if needed.
5.6.2.2
Counter outputs
X6
Function
Type
LED
Description
1
Sys DC 24V
I
green
1L+: DC 24V for electronic section supply
2
Sys 0V
I
1M: GND for electronic section supply
3
Shield
I
Shield
4
AGND
I
GND for analog inputs
5
AI 0
I
Analog input AI 0
6
AI 1
I
Analog input AI 1
7
DO 1.0
O
green
Digital output DO 8
8
DO 1.1
O
green
Digital output DO 9
9
DO 1.2
O
green
Digital output DO 10
10
DO 1.3
O
green
Digital output DO 11
Input signals
X6: DC 24V, AI, DO byte 1
VIPA System MICRO
Deployment I/O periphery
Counting > Wiring
HB400 | CPU | M13-CCF0000 | en | 16-47