Counter...
2 7
Counter
...
–
For parametrization of the digital I/O periphery and the technological
functions the corresponding sub modules of the CPU 314C-2 PN/DP
(314-6EH04-0AB0 V3.3) is to be used.
–
The controlling of the operating modes of the technological functions
happens by means of handling blocks of the user program.
Since the CPU from VIPA is configured as Siemens CPU, so the setting of the non- VIPA
specific parameters takes place via the Siemens CPU. For parametrization click in the
Project area
respectively in the
Device overview
at the CPU part. Then the parameters of
the CPU part are shown in the
Properties dialog
. Here you can make your parameter set-
Chapter 4.7 ‘Setting standard CPU parameters’ on page 63
1.
Switch in the
Project area
to
‘Network view’
.
2.
After installing the GSDML the IO device for the CPU may be found in the hardware
catalog at
Other field devices > PROFINET > IO > VIPA GmbH > VIPA MICRO
PLC
. Connect the slave system to the CPU by dragging&dropping it from the hard-
ware catalog to the
Network view
and connecting it via PROFINET to the CPU.
3.
Click in the
Network view
at the PROFINET part of the Siemens CPU and enter at
valid IP address data in
‘Properties’
at
‘Ethernet address’
in the area
‘IP protocol’
.
4.
Enter at
‘PROFINET’
a
‘PROFINET device name’
. The device name must be
unique at the Ethernet subnet.
5.
Select in the
Network view
the IO device
‘VIPA MICRO PLC’
and switch to the
Device overview
.
ð
In the
Device overview
of the PROFINET IO device
‘VIPA MICRO PLC’
the
CPU is already placed at slot 0. From slot 1 you can place your Extension
module.
Setting standard CPU
parameters
Connection CPU as
PROFINET IO device
VIPA System MICRO
Configuration with TIA Portal
TIA Portal - Hardware configuration - CPU
HB400 | CPU | M13-CCF0000 | en | 16-47
204