At stationary operation it is convenient to strip the insulated cable interruption free
and lay it on the isolation/protected earth conductor line.
n
To fix the isolation tangles use cable clamps out of metal. The clamps must clasp the
isolation extensively and have well contact.
n
Lay the isolation on an isolation rail directly after the entry of the cable in the cabinet.
Lead the isolation further on to your PLC and don't lay it on there again!
CAUTION!
Please regard at installation!
At potential differences between the grounding points, there may be a
compensation current via the isolation connected at both sides.
Remedy: Potential compensation line
2.8 General data
Conformity and approval
Conformity
CE
2014/35/EU
Low-voltage directive
2014/30/EU
EMC directive
Approval
UL
-
Refer to Technical data
others
RoHS
2011/65/EU
Restriction of the use of certain hazardous substances in
electrical and electronic equipment
Protection of persons and device protection
Type of protection
-
IP20
Electrical isolation
to the field bus
-
electrically isolated
to the process level
-
electrically isolated
Insulation resistance
-
-
Insulation voltage to reference earth
Inputs / outputs
-
AC / DC 50V, test voltage AC 500V
Protective measures
-
against short circuit
Environmental conditions to EN 61131-2
Climatic
Storage / transport
EN 60068-2-14
-25…+70°C
Operation
Horizontal installation hanging
EN 61131-2
0…+60°C
VIPA System MICRO
Basics and mounting
General data
HB400 | CPU | M13-CCF0000 | en | 16-47