5.3.4.2
Filter
The analog input part has a filter integrated. The parametrization of the filter happens in
the Siemens SIMATIC Manager via the parameter
‘Integration time’
. The default value of
the filter is 1000ms. The following values can be entered:
n
‘Input 0
≙
Channel 0’
‘Input 1
≙
Channel 1’
–
‘Integration time 2.5ms’
≙
2ms (no filter)
–
‘Integration time 16.6ms’
≙
100ms (small filter)
–
‘Integration time 20ms’
≙
1000ms (medium filter)
By using the record set 1 of the SFC 55 "WR_PARM" you may alter the parametrization
in the module during runtime.
The time needed until the new parametrization is valid can last up to 2ms.
During this time, the measuring value output is 7FFFFh.
Record set 1
Byte
Bit 7 ... Bit 0
Default
0
Bit 7...0: reserved
00h
1
Filter
n
Bit 1, 0: Analog input channel 0
Bit 3, 2: Analog input channel 1
–
00b:
‘Integration time 2.5ms’
≙
2ms (no filter)
–
01b:
‘Integration time 16.6ms’
≙
100ms (small filter)
–
10b:
‘Integration time 20ms’
≙
1000ms (medium filter)
n
Bit 7...4: reserved
10h
2...12
Bit 7...0: reserved
5.4 Digital input
5.4.1 Properties
n
16xDC 24V
n
Maximum input frequency
–
10 inputs: 100kHz
–
6 inputs: 1kHz
n
Interrupt functions parameterizable
n
Status indication via LEDs
Parameter hardware con-
figuration
Parametrization during
runtime
VIPA System MICRO
Deployment I/O periphery
Digital input > Properties
HB400 | CPU | M13-CCF0000 | en | 16-47
90