For parametrization click at the CPU at slot 0 in the
Device overview
of the PROFINET IO
device
‘VIPA MICRO PLC’
. Then the parameters of the CPU part are shown in the
Prop-
erties dialog
. Here you can make your parameter settings.
specific CPU parameters’ on page 66
10.3 TIA Portal - Hardware configuration - Ethernet PG/OP channel
The CPU has an integrated Ethernet PG/OP channel. This channel allows you to pro-
gram and remote control your CPU.
n
The Ethernet PG/OP channel (X3/X4) is designed as switch. This enables PG/OP
communication via the connections X3 and X4.
n
The Ethernet PG/OP channel also gives you access to the internal web page that
contains information about firmware version, connected I/O devices, current cycle
times etc.
n
At the first commissioning respectively after a factory reset the Ethernet PG/OP
channel has no IP address.
n
For online access to the CPU via the Ethernet PG/OP channel, valid IP address
parameters have to be assigned to this. This is called "initialization".
n
This can be done with the Siemens TIA Portal.
1.
Install your System MICRO with your CPU.
2.
Wire the system by connecting cables for voltage supply and signals.
3.
Connect the one of the Ethernet jacks (X3, X4) of the Ethernet PG/OP channel to
Ethernet.
4.
Switch on the power supply.
ð
After a short boot time the CP is ready for communication. He possibly has no
IP address data and requires an initialization.
The initialization via the Online functions takes place with the following proceeding:
Determine the current Ethernet (MAC) address of your Ethernet PG/OP channel.
This can be found at the front of the CPU labelled as "MAC PG/OP: ...".
Setting VIPA specific CPU
parameters
Overview
Assembly and commis-
sioning
"Initialization" via Online
functions
VIPA System MICRO
Configuration with TIA Portal
TIA Portal - Hardware configuration - Ethernet PG/OP channel
HB400 | CPU | M13-CCF0000 | en | 16-47