Byte 0,
bit 6
Warning
Indicates that the Inverter detected a
warning.
0: Normal
1: Warning detected.
Byte 0,
bit 7
Faulted
Indicates that the Inverter detected a
fault.
0: Normal
1: Fault detected.
Byte 1,
bit 0
Terminal
S1
Indicates the input status of Inverter
multi-function input terminal S1. When
using this terminal as a general-purpose
DI terminal, always set Inverter constant
n050 to 28.
0: Terminal S1 OFF
1: Terminal S1 ON
Byte 1,
bit 1
Terminal
S2
Indicates the input status of Inverter
multi-function input terminal S2. When
using this terminal as a general-purpose
DI terminal, always set Inverter constant
n051 to 28.
0: Terminal S2 OFF
1: Terminal S2 ON
Byte 1,
bit 2
Terminal
S3
Indicates the input status of Inverter
multi-function input terminal S3. When
using this terminal as a general-purpose
DI terminal, always set Inverter constant
n052 to 28.
0: Terminal S3 OFF
1: Terminal S3 ON
Data
Name