114
* 1. When a 400 V Class Inverter is being used, the value will be 0190 Hex
(400 V).
01
16
Speed
Scale
Sets or references
the unit coefficient
(n153) for speed-
related data.
Speed units: 1 (r/
min) x 1/2
SS
SS
: Speed scale
setting
-15 to
15
(F1 to
0F)
00
OK
OK
Byte
17
Current
Scale
Sets or references
the unit coefficient
(n154) for current-
related data.
Current units: 0.1
(A) x 1/2
CS
CS
: Current scale
setting
-15 to
15
(F1 to
0F)
00
OK
OK
Byte
1A
Power
Scale
Sets or references
the unit Coefficient
(n155) for power-
related data.
Power units: 1 (W)
x 1/2
PS
PS
: Power scale
setting
-15 to
15
(F1 to
0F)
00
OK
OK
Byte
1B
Voltage
Scale
Sets or references
the unit coefficient
(n156) for voltage-
related data.
Voltage units: 1 (V)
x 1/2
VS
VS
: Voltage scale
setting
-15 to
15
(F1 to
0F)
00
OK
OK
Byte
1C
Time
Scale
Sets or references
the unit coefficient
(n157) for time-re-
lated data.
Time units: 1 (ms)
x 1/2
TS
TS
: Time scale set-
ting
-15 to
15
(F1 to
0F)
00
OK
OK
Byte
1D
Ref
From
Net
Indicates which
Frequency Refer-
ence input has
been selected in
the Inverter. (See
note 4.)
00: A Frequency
Reference input
other than De-
viceNet is enabled.
01: The Frequen-
cy Reference input
from DeviceNet is
enabled.
---
00
OK
---
Byte
In-
stance
At-
tribute
Name
Contents
Setting
Range
Factory Set-
ting (Hex)
Read Write
Size