7. Programming Features
165
Factory Settings
Note: Terminal MA can be used only from DeviceNet communications. There
is no corresponding external output terminal.
8
Low torque detected,
NO output
-
-
9
Low torque detected,
NC output
-
-
10
Minor fault
Closed when an alarm has been
detected.
-
11
Baseblocked
Closed when the Inverter output
is OFF.
-
12
Operating mode
Closed when LOCAL is selected
for the LOCAL/REMOTE selec-
tion.
-
13
Inverter operation ready
Closed when an Inverter fault is
not detected, and operation is
ready.
-
14
Fault restart
Closed during fault retries.
-
15
UV
Closed when undervoltage is de-
tected.
-
16
Reverse run
Closed during reverse run.
-
17
Speed search
Closed when Inverter conducts a
speed search.
-
18
Data output from com-
munications
-
19
PID feedback loss
Closed during PID feedback loss
183
20
Frequency reference
loss
-
-
21
Inverter overheat alert
(OH3)
-
-
No.
Terminal
Factory Setting
n057
MA (See note.)
2 (frequency agree)
n058
P1
1 (operating)
n059
P2
0 (fault)
Setting
Name
Description
Ref.