![YASKAWA Varispeed V7 Instruction Manual Download Page 104](http://html1.mh-extra.com/html/yaskawa/varispeed-v7/varispeed-v7_instruction-manual_3554366104.webp)
6. Operating with DeviceNet Communications
103
Motor Data Object (Class 28 Hex)
The Motor Data object is the object that manages information and func-
tions related to the motor connected to the Inverter. The motor’s rated
current and rated voltage can be set or referenced with this object.
• Supported Services
02
0C
Watch-
dog tim-
eout
action
Indicates the ac-
tion to take when a
timeout occurred
during internal pro-
cessing related to
communications.
00: Maintain until
reset or discon-
nected.
01: Disconnect au-
tomatically.
02: Perform the
operation again
while connected.
---
00
OK
---
Byte
0D
Pro-
duced
connec-
tion path
length
Indicates the
transmission con-
nection path’s
number of bytes.
---
0003
OK
---
Word
0E
Pro-
duced
connec-
tion path
Indicates the appli-
cation object that
transmits data
from the instance.
---
62,34,37
OK
---
Array
0F
Con-
sumed
connec-
tion path
length
Indicates the re-
ception connection
path’s number of
bytes.
---
0003
OK
---
Word
10
Con-
sumed
connec-
tion path
Indicates the appli-
cation object that
receives data from
the instance.
---
62,31,35
OK
---
Array
Service
Code
(Hex)
Service Name
Description
0E
Get_Attribute_
Single
Returns the contents of the specified
attribute.
10
Set_Attribute_
Single
Changes the contents of the speci-
fied attribute.
In-
stance
At-
tribute
Name
Contents
Setting
Range
Factory Set-
ting (Hex)
Read Write
Size