246
Third Functions (Constants n080 to n119)
No.
Register
No. for
Trans-
mission
Name
Setting
Range
Setting Unit
Factory
Setting
User
Setting
Ref.
Page
080
0150
Carrier Frequency Se-
lection
1 to 4, 7 to
9
1
4 (Note 4)
151
081
0151
Momentary Power Loss
Ridethrough Method
0 to 2
1
0
144
082
0152
Automatic Retry At-
tempts
0 to 10
times
1
0
148
083
0153
Jump Frequency 1
0.00 to
400.0 Hz
0.01 Hz (less
than 100 Hz)/
0.1 Hz (100 Hz
or more)
0.00 Hz
148
084
0154
Jump Frequency 2
0.00 to
400.0 Hz
0.01 Hz (less
than 100 Hz)/
0.1 Hz (100 Hz
or more)
0.00 Hz
148
085
0155
Jump Frequency 3
0.00 to
400.0 Hz
0.01 Hz (less
than 100 Hz)/
0.1 Hz (100 Hz
or more)
0.00 Hz
148
086
0156
Jump Frequency Range
0.00 to
25.50 Hz
0.01 Hz
0.00 Hz
148
089
0159
DC Injection Braking
Current
0% to
100%
1%
50%
150
090
015A
DC Injection Braking
Time at Stop
0.0% to
25.5%
0.1s
0.5s
(Note 2)
156
091
015B
DC Injection Braking
Time at Startup
0.0% to
25.5%
0.1s
0.0s
150
092
015C
Stall Prevention During
Deceleration
0.1
1
0
170
093
015D
Stall Prevention Level
During Acceleration
30% to
200%
1%
170%
167
094
015E
Stall Prevention while
Running
30% to
200%
1%
160%
168
095
015F
Frequency Detection
Level (Multi-function
Contact Output)
0.00 to
400.0 Hz
0.01 Hz (less
than 100 Hz)/
0.1 Hz (100 Hz
or more)
0.00 Hz
147
096
0160
Overtorque Detection
Function Selection 1
0 to 4
1
0
146
097
0161
Overtorque Detection
Function Selection 2
0.1
1
0
147
098
0162
Overtorque Detection
Level
30% to
200%
1%
160%
147
099
0163
Overtorque Detection
Time
0.1 to
10.0 s
0.1 s
0.1 s
147
100
0164
Hold Output Frequency
Saving Selection
0.1
1
0
161
103
0167
Torque Compensation
Gain
0.0 to 2.5
0.1
1.0
131