7. Programming Features
137
REMOTE Mode
1. Select remote mode.
There are following two methods to select remote mode.
• Select rE (remote mode) for the
selection.
• When the local/remote switching function is selected for the
multi-function input selection, turn OFF the input terminal to
select remote mode.
2. Select the operation method by setting constant n003.
n003=0: Enables the Digital Operator (same with local mode).
=1: Enables the multi-function input terminal (see fig. below).
=3: Enables DeviceNet communications.
• Example when using the multi-function input terminal as opera-
tion reference (two-wire sequence)
For an example of three-wire sequence, refer to page 159.
Note: When the Inverter is operated without the Digital Operator, always set
constant n010 to 0.
Operating (RUN/STOP Commands) Using DeviceNet Com-
munications
Setting constant n003 to 3 in REMOTE mode enables using RUN/
STOP commands via DeviceNet communications. For commands using
DeviceNet communications, refer to page 55.
Selecting Frequency Reference
Select REMOTE or LOCAL mode in advance. For the method for
selecting the mode, refer to page 135.
LOCAL Mode
Select command method using constant n008.
n008=0: Enables using the potentiometer on the Digital Operator.
=1: Enables digital setting on the Digital Operator
(factory setting).
The factory setting for models with the Digital Operator
with a potentiometer (JVOP-140) is n008=0.
FWD RUN/STOP
REV RUN/STOP
n003: 1 (Factory setting: 0)
n050: 1 (Factory setting)
n051: 2 (Factory setting)