12 Fault Diagnosis and Possible Solutions
38
YASKAWA EUROPE GMBH
YEU SIEP C710616 86A - AC Drive A1000 Option Powerlink - Technical Manual
Digital Operator Display
Fault Name
oFA00
Powerlink Option Card Fault
The drive does not support the option board plugged in.
Cause
Possible Solution
Non-compatible option connected to the drive.
1. Check drive firmware version as described on page
2. If drive firmware version is correct, replace option card.
3. Replace the drive.
Digital Operator Display
Fault Name
oFA01
Powerlink Option Card Fault
Option card is not properly connected.
Cause
Possible Solution
Problem with the connectors between the drive and Powerlink
Option.
Turn the power off and check the connectors between the drive and Powerlink
Option.
Digital Operator Display
Fault Name
to
oFA30 and oFA32
Option card has detected a Communication Option card ID error
Option card has detected a Sum check error
Cause
Possible Solution
Drive system is overloaded.
Force Powerlink state change to NOT_ACTIVE/BASIC_ETHERNET
Drive is not properly processing the state.
Digital Operator Display
Fault Name
to
oFA30 to oFA43
Powerlink Option Card Fault
Communication ID error
Cause
Possible Solution
Option card hardware fault
Replace the Powerlink
Option. Contact YASKAWA for assistance.
Digital Operator Display
Fault Name
oFb00
Option Card Fault at Connector CN5-B
Non-compatible option card is connected.
Cause
Possible Solution
The Powerlink
option card has been plugged into option port
CN5-B.
Always use option port CN5-A for communication option cards.
Digital Operator Display
Fault Name
oFb02
Option Card Fault at Connector CN5-B
Two of the same option cards are connected at the same time.
Cause
Possible Solution
Two or more input option cards (analog, digital or
communication) have been connected to the drive at the same
time.
Use either an analog input option AI-A3 or a digital input option DI-A3 or a communication option card. Never use two of
these cards at the same time.
Digital Operator Display
Fault Name
oFc00
Option Card Fault at Connector CN5-C
Non-compatible option card is connected.
Drive is not processing the internal interface protocol. Drive does not support Powerlink option card
Cause
Possible Solution
The Powerlink
option card has been plugged into option port
CN5-C.
Always use option port CN5-A for communication option cards.
Digital Operator Display
Fault Name
oFc02
Option Card Fault at Connector CN5-C
Two of the same option cards are connected at the same time.
Cause
Possible Solution
Two or more input option cards (analog, digital or
communication) have been connected to the drive at the same
time.
Use either an analog input option AI-A3 or a digital input option DI-A3 or a communication option card. Never use two of
these cards at the same time.