4.1 Alarm Displays
4.1.2 Troubleshooting Alarms
4-3
4
Maintenance
4.1.2
Troubleshooting Alarms
The causes of and corrections for the alarms are given in the following table. Contact your
Yaskawa representative if you cannot solve a problem with the correction given in the table.
4.1.3
Resetting Motor Type Alarms
The SERVOPACK automatically determines the type of motor that is connected to it. If the type
of motor that is connected is changed, an A.070 alarm (Motor Type Change Detected) will
occur the next time the SERVOPACK is started. If an A.070 alarm occurs, you must set the
parameters to match the new type of motor.
An A.070 alarm is reset by executing the Reset Motor Type Alarm utility function.
This functionality is supported by the following SERVOPACKs.
•
Σ
-7S SERVOPACKs with Analog Voltage/Pulse Train References
•
Σ
-7S SERVOPACKs with MECHATROLINK-II Communications References
•
Σ
-7S SERVOPACKs with MECHATROLINK-III Communications References
•
Σ
-7W SERVOPACKs with MECHATROLINK-III Communications References
Preparations
Check the following setting before you execute the Reset Motor Type Alarm utility function.
•
The parameters must not be write prohibited.
Applicable Tools
Alarm Number:
Alarm Name
Possible Cause
Confirmation
Correction
Refer-
ence for
Correction
A.070:
Motor Type
Change Detected
(The connected
motor is a differ-
ent type of motor
from the previ-
ously connected
motor.)
A Rotary Servomotor
was removed and a
Linear Servomotor
was connected.
–
Set the parameters for a
Linear Servomotor and
reset the motor type
alarm. Then, turn the
power supply to the SER-
VOPACK OFF and ON
again.
A Linear Servomotor
was removed and a
Rotary Servomotor
was connected.
–
Set the parameters for a
Rotary Servomotor and
reset the motor type
alarm. Then, turn the
power supply to the SER-
VOPACK OFF and ON
again.
1. This utility function is the only way to reset an A.070 alarm (Motor Type Change Detected).
The errors are not reset when you reset alarms or turn OFF the power supply to the SER-
VOPACK.
2. If an A.070 alarm occurs, first set the parameters according to the newly connected motor
type and then execute the Reset Motor Type Alarm utility function.
Tool
Function
Reference
Panel Operator
Fn021
Operating Procedure with Panel Operator
Digital Operator
Fn021
Operating Procedure with Digital Operator
S
Setup − Reset Motor Type
Alarm
–
Information