1.2 Forcing the Motor to Stop
1.2.2 Setting the FSTP (Forced Stop Input) Signal
1-11
1
Application Function
s
1.2.2
Setting the FSTP (Forced Stop Input) Signal
When you allocate the FSTP (Forced Stop Input) signal, the forced stop function will be
enabled. Use Pn516 = n.
X (FSTP (Forced Stop Input) Signal Allocation) to allocate the
FSTP signal to a connector pin.
•
Σ
-7S SERVOPACKs with Analog Voltage/Pulse Train References
•
Σ
-7S SERVOPACKs with MECHATROLINK-II Communications References or
Σ
-7S SERVO-
PACKs with MECHATROLINK-III Communications References
Parameter
Description
When
Enabled
Classifi-
cation
Pn516
n.
0
Enable drive when CN1-40 input signal is ON (closed).
After
restart
Setup
n.
1
Enable drive when CN1-41 input signal is ON (closed).
n.
2
Enable drive when CN1-42 input signal is ON (closed).
n.
3
Enable drive when CN1-43 input signal is ON (closed).
n.
4
Enable drive when CN1-44 input signal is ON (closed).
n.
5
Enable drive when CN1-45 input signal is ON (closed).
n.
6
Enable drive when CN1-46 input signal is ON (closed).
n.
7
Set the signal to always prohibit drive (always force the
motor to stop).
n.
8
(default set-
ting)
Set the signal to always enable drive (always disable forc-
ing the motor to stop).
n.
9
Enable drive when CN1-40 input signal is OFF (open).
n.
A
Enable drive when CN1-41 input signal is OFF (open).
n.
B
Enable drive when CN1-42 input signal is OFF (open).
n.
C
Enable drive when CN1-43 input signal is OFF (open).
n.
D
Enable drive when CN1-44 input signal is OFF (open).
n.
E
Enable drive when CN1-45 input signal is OFF (open).
n.
F
Enable drive when CN1-46 input signal is OFF (open).
Parameter
Description
When
Enabled
Classifi-
cation
Pn516
n.
0
Enable drive when CN1-13 input signal is ON (closed).
After
restart
Setup
n.
1
Enable drive when CN1-7 input signal is ON (closed).
n.
2
Enable drive when CN1-8 input signal is ON (closed).
n.
3
Enable drive when CN1-9 input signal is ON (closed).
n.
4
Enable drive when CN1-10 input signal is ON (closed).
n.
5
Enable drive when CN1-11 input signal is ON (closed).
n.
6
Enable drive when CN1-12 input signal is ON (closed).
n.
7
Set the signal to always prohibit drive (always force the
motor to stop).
n.
8
(default set-
ting)
Set the signal to always enable drive (always disable forc-
ing the motor to stop).
n.
9
Enable drive when CN1-13 input signal is OFF (open).
n.
A
Enable drive when CN1-7 input signal is OFF (open).
n.
B
Enable drive when CN1-8 input signal is OFF (open).
n.
C
Enable drive when CN1-9 input signal is OFF (open).
n.
D
Enable drive when CN1-10 input signal is OFF (open).
n.
E
Enable drive when CN1-11 input signal is OFF (open).
n.
F
Enable drive when CN1-12 input signal is OFF (open).
Summary of Contents for SERVOPACK Sigma 7S Series