3.1 Main Circuit Wiring
3-3
3
Wiring and Connection
∗1.
Do not short-circuit the B1/
and B2 terminals. Doing so may damage the SERVOPACK.
∗2.
The
1 and
2 terminals are short-circuited with a jumper at the factory.
3.1.2
Using a Standard Power Supply Input (Single-phase 100-V, Three-phase
200-V, or Three-phase 400-V)
(1) Wire Types
Use the following type of wire for main circuit.
The following table shows the wire sizes and allowable currents for three wires. Use wires with specifications equal to or
less than those shown in the table.
•
600 V grade heat-resistant polyvinyl chloride insulated wire (HIV)
Note: The values in the table are for reference only.
B1/
Main circuit plus
terminal
A
D
Use when DC power supply input is used.
2
or
Main circuit
minus terminal
A
D
U, V, W
Linear
servomotor
connection
terminals
Use for connecting to the linear servomotor.
Ground
terminals (x2)
Use for connecting the power supply ground terminal and linear servomo-
tor ground terminal.
Terminal Symbols
Name
Model SGDV-
Description
Cable Type
Allowable Conductor
Temperature
°
C
Symbol
Name
IV
600 V polyvinyl chloride insulated wire
60
HIV
600 V grade heat-resistant polyvinyl chloride insulated wire
75
AWG Size
Nominal
Cross Section
Diameter
(mm
2
)
Configuration
(Number of
Wires/mm
2
)
Conductive
Resistance
(
Ω
/km)
Allowable Current at Surrounding Air
Temperature (A)
30
°
C
40
°
C
50
°
C
20
0.5
19/0.18
39.5
6.6
5.6
4.5
19
0.75
30/0.18
26.0
8.8
7.0
5.5
18
0.9
37/0.18
24.4
9.0
7.7
6.0
16
1.25
50/0.18
15.6
12.0
11.0
8.5
14
2.0
7/0.6
9.53
23
20
16
12
3.5
7/0.8
5.41
33
29
24
10
5.5
7/1.0
3.47
43
38
31
8
8.0
7/1.2
2.41
55
49
40
6
14.0
7/1.6
1.35
79
70
57
4
22.0
7/2.0
0.85
91
81
66