8.1 EN Standard Compliant I/O Modules
8-5
8
8.1.3
EN Standards
The I/O Modules complies with the following EN Standards.
However, reconfirmation is required after being installed in the final product because
these products are built-in type devices.
• EN61131-1
• EN61131-2
1) Differences from Standard Modules
The I/O Modules differ from the standard Modules in the following items.
• Removable terminal block
2) Conditions Low Voltage Directive
The following conditions must be satisfied to conform to the Low Voltage Directive.
a) Terminal block
• Use terminal blocks that are certified as the Low Voltage Directive compliant
products.
• The terminal blocks of the I/O Modules complies with the Low Voltage Directive.
To identify these terminal blocks, the shape of the field wiring terminals and the
color of the terminal block mounting screws are different from standard terminal
blocks as shown in the following table.
Note:
For the field wiring terminals, make sure to use the terminal block provided
with the product.
If other terminal blocks are used, the product does not comply with the Low
Voltage Directive.
Low Voltage Directive
One of the requirements under the European Electrical Safety Regulations.
It applies to the electrical equipment designed to operate in the voltage range 50 VAC
to 1000 VAC or 75 VDC to 1500 VDC.
Specifications
Standard Terminal Block
EN Standard Compliant
Terminal Block
Shape of field wiring
terminals
With square washers
With round washers
Color of screws
Silver (nickel plated)
Black
TERMS