3.2 Digital Output Module Specifications
3-25
3
2) The following diagram shows the circuit configuration.
If using a 100/200-VAC 8-point Output Module, connect a fuse, which complies with
the load specifications, in series with the load.
A protective fuse does not built into the following 100/200-VAC 8-point Output
Modules. If a fuse is not connected, fire or damage to the devices or output cir-
cuits may occur if the load is short-circuited or the circuit overloaded.
Insulation Resistance
100 M
Ω
min. at room temperature and humidity between input termi-
nals and ground
(measured with a 500-VDC test voltage megohmmeter).
External Power Supply
100/200 VAC supplied to drive loads
Derating Conditions
None
Internal Current Consumption
50 mA max. at 5 VDC (with all points ON)
Maximum Heating Value
9.0 W
Hot Swapping
(Removal/insertion under power)
Permitted
Approx. Mass
300 g
External Dimensions
40.3
×
130
×
103.9 mm (W
×
H
×
D)
Item
Specifications
Output 1
Output 8
100/200 VAC
100/200 VAC
Output signal
indicator
From CPU
Phototriac
Internal circuits
CAUTION