5.4 Operations Using MEMOSOFT
5-25
5
5) Timeout Output Status Setting (Only for Register Output Module)
Make sure that the Parameter Setting Screen (I/O Map Module Editor) is being dis-
played.
(1) Move the cursor to
Time out
and press the
Enter
Key to access the timeout
output setting.
Fig. 5.17 Parameter Setting Screen: Timeout Output
(2) A screen appears so that the timeout output setting can be selected.
Move the cursor to either
Clear
or
Retain
and press the
Enter
Key to select
the desired timeout output status. If
Retain
is selected, the data just before the
CPU Module entered STOP status will be sent for all outputs until the CPU
Module returns to RUN status.
The MEMOSOFT is set by default to
Clear
.
Fig. 5.18 Timeout Output Status Selection
This Timeout output setting is only for Register Output Modules, but not for Register
Input Module.