3 Digital I/O Specifications
3.1.1 100-VAC 16-point Input Module
3-2
3.1
Digital Input Module specifications
3.1.1 100-VAC 16-point Input Module - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-2
3.1.2 200-VAC 16-point Input Module - - - - - - - - - - - - - - - - - - - - - - - - - - - 3-6
3.1.3 12/24-VDC 16-point Input Module - - - - - - - - - - - - - - - - - - - - - - - - - 3-10
3.1.4 12/24-VDC 32-point Input Module - - - - - - - - - - - - - - - - - - - - - - - - - 3-14
3.1.5 12/24-VDC 64-point Input Module - - - - - - - - - - - - - - - - - - - - - - - - - 3-18
3.1.1
100-VAC 16-point Input Module
1) Performance Specifications
This section describes the performance specifications, circuit configuration, external
connections, and the external appearance of the 120-series Digital Input Modules.
Item
Specifications
Name
100-VAC 16-point Input Module
Model Name
AC100IN-16P
Model No.
JAMSC-120DAI54300
Rated Voltage
100 VAC
Maximum Allowable Voltage
132 VAC
Rated Frequency
50/60 Hz
Allowable Frequency Range
47 to 63 Hz
Inrush Current
160 mA
Rated Current
7 mA (at 100 VAC, 50 Hz)
Input Impedance
14.3 k
Ω
(at 100 VAC, 50 Hz)
12.5 k
Ω
(at 100 VAC, 50 Hz)
Standard Operating Ranges
ON voltage range: 74 to 132 VAC
OFF voltage range: 30 VAC max.
Input Type
AC type2 (according to JIS B3502)
Input Delay Times
OFF to ON: 20 ms max.
ON to OFF: 35 ms max.
Number of common
2
Number of Inputs per Common
8 points/common
Input Power Supply per Common
Connect power supplies of the same phase to the Common 1 and
Common 2.
External Connections
Removable terminal block with M3 screw terminals
Number of Inputs
16
Input Signal Indication
Indicator for each point; lit when the input is ON.
Status saved in internal logic.
Status Indication
ACTIVE: Lights during input processing
Insulation Method
Photocoupler
Dielectric Strength
1,500 VAC for 1 min or 1,800 VAC for 1 s between input terminals and
internal circuits and between all input commons.
Insulation Resistance
100 M
Ω
min. at room temperature and humidity between input termi-
nals and ground
(measured with a 500-VDC test voltage megohmmeter).
External Power Supply
100 VAC supplied to signals
Derating Conditions
None
Internal Current Consumption
90 mA max. at 5 VDC (with all points ON)