158
YASKAWA
TOEPC71061737D GA800 DRIVE INSTALLATION & PRIMARY OPERATION
Code
Name
Causes
Possible Solutions
These settings do not agree:
•
A PG-RT3 option is connected to the drive.
•
H1-xx = 16 [Motor 2 Selection]
is set.
Correct the parameter settings.
Note:
The Motor Switch function is not available with the PG-RT3
option.
oPE05
Run Cmd/Freq Ref Source Sel Err
The setting to assign the Run command or frequency
reference to an option card or the pulse train input is
incorrect.
Correct the parameter settings.
b1-01 = 3 [Frequency Reference Selection 1 =
Option PCB]
is set, but there is no option card
connected to the drive.
b1-02 = 3 [Run Command Selection 1 = Option
PCB]
is set, but there is no option card connected to
the drive.
Connect an option card to the drive.
The following parameters are set at the same time:
•
b1-01 = 4 [Pulse Train Input]
•
H6-01 ≠ 0 [Terminal RP Pulse Train Function ≠
Frequency Reference]
Set
H6-01 = 0
.
The following parameters are set at the same time:
•
F3-01 = 6 [Digital Input Function Selection =
BCD (5-digit), 0.01 Hz]
•
F3-03 = 0, 1 [Digital Input Data Length Select =
8-bit, 12-bit]
Set
F3-03 = 2 [16-bit]
.
These parameters are set and there is an AI-A3 option
card connected to the drive:
•
H1-xx = 2 [External Reference 1/2 Selection]
•
b1-15 = 3 [Frequency Reference Selection 2 =
Option PCB]
•
F2-01 = 0 [Analog Input Function Selection = 3
Independent Channels]
Correct the parameter settings.
oPE06
Control Method Selection Error
A1-02 = 1, 3, or 7 [Control Method Selection = CL-
V/f, CLV, CLV/PM]
, but there is no encoder option
connected the drive.
•
Connect an encoder option the drive.
•
Set
A1-02
correctly.
You supplied external 24 V power to terminals PS-
AC when:
•
There is an encoder option installed the drive
•
The drive main circuit power supply is de-
energized
1.
De-energize the drive main circuit power supply and the
external 24 V power supply to terminals PS-AC.
2.
After the keypad display goes out, energize the drive main
circuit power supply again.
3.
Supply the external 24 V power to terminals PS-AC.
When you use an encoder option, energize the drive main circuit
power supply.
oPE07
Analog Input Selection Error
The settings for
H3-02, H3-06, and H3-10 [MFAI
Function Select]
and
H7-30 [Virtual Analog Input
Selection]
overlap.
Set
H3-02, H3-06, H3-10, and H7-30
correctly to prevent overlap.
Note:
It is possible to set these functions to multiple analog input
terminals at the same time:
•
Setting value
0 [Frequency Reference]
•
Setting values
F and 1F [Not Used]
The following parameters are set at the same time:
•
H3-02, H3-06, H3-10, H7-30 = B [PID Feedback]
•
H6-01 = 1 [Terminal RP Pulse Train Function =
PID Feedback Value]
The following parameters are set at the same time:
•
H3-02, H3-06, H3-10, H7-30 = C [PID Setpoint]
•
H6-01 = 2 [PID Setpoint Value]
The following parameters are set at the same time:
•
H3-02, H3-06, H3-10, H7-30 = C
•
b5-18 = 1 [b5-19 PID Setpoint Selection =
Enabled]
The following parameters are set at the same time:
•
H6-01 = 2
•
b5-18 = 1
Remove the function settings that are not in use.
oPE08
Parameter Selection Error
You set a function that is not compatible with the
control method set in
A1-02 [Control Method
Selection]
.
1.
Push
to show
U1-18 [oPE Fault Parameter]
, and find
parameters that are not in the applicable setting range.
2.
Correct the parameter settings.
Note:
If more than one error occurs at the same time, other
oPExx
errors have priority over
oPE02
.