120
YASKAWA
TOEPC71061737D GA800 DRIVE INSTALLATION & PRIMARY OPERATION
Model
Terminal
Recomm. Gauge
mm
2
Applicable Gauge
(IP20 Applicable Gauge
)
mm
2
Wire Stripping
Length
mm
Terminal Screw
Size and Shape
Tightening Torque
N
∙
m (lbf
∙
in)
4208
R/L1, S/L2, T/L3
50 × 2P
25 - 95 × 2P
(70 - 95 × 2P)
-
M10
20
(177)
U/T1, V/T2, W/T3
50 × 2P
25 - 95 × 2P
(70 - 95 × 2P)
-
M10
20
(177)
-, +1
70 × 2P
35 - 120 × 2P
(120 × 2P)
-
M10
20
(177)
+3
35 × 2P
25 - 70 × 2P
(70 × 2P)
-
M10
20
(177)
50
50 - 240
(-)
-
M10
18 - 23
(159 - 204)
4250
R/L1, S/L2, T/L3
50 × 2P
25 - 95 × 2P
(70 - 95 × 2P)
-
M10
20
(177)
U/T1, V/T2, W/T3
50 × 2P
25 - 95 × 2P
(70 - 95 × 2P)
-
M10
20
(177)
-, +1
70 × 2P
35 - 120 × 2P
(120 × 2P)
-
M10
20
(177)
+3
50 × 2P
25 - 70 × 2P
(70 × 2P)
-
M10
20
(177)
70
70 - 240
(-)
-
M10
18 - 23
(159 - 204)
4302
R/L1, S/L2, T/L3
70 × 2P
25 - 95 × 2P
(70 - 95 × 2P)
-
M10
20
(177)
U/T1, V/T2, W/T3
70 × 2P
25 - 95 × 2P
(70 - 95 × 2P)
-
M10
20
(177)
-, +1
95 × 2P
35 - 120 × 2P
(120 × 2P)
-
M10
20
(177)
+3
70 × 2P
25 - 70 × 2P
(70 × 2P)
-
M10
20
(177)
95
95 - 240
(-)
-
M10
18 - 23
(159 - 204)
4371
R/L1, S/L2, T/L3
120 × 2P
70 - 150 × 2P
(150 × 2P)
-
M12
35
(310)
U/T1, V/T2, W/T3
120 × 2P
70 - 150 × 2P
(150 × 2P)
-
M12
35
(310)
-, +1
120 × 2P
95 - 185 × 2P
(185 × 2P)
-
M12
35
(310)
+3
70 × 2P
50 - 95 × 2P
(-)
-
M12
35
(310)
120
120 - 240
(-)
-
M12
32 - 40
(283 - 354)
4414
R/L1, S/L2, T/L3
120 × 2P
70 - 150 × 2P
(150 × 2P)
-
M12
35
(310)
U/T1, V/T2, W/T3
120 × 2P
70 - 150 × 2P
(150 × 2P)
-
M12
35
(310)
-, +1
120 × 2P
95 - 185 × 2P
(185 × 2P)
-
M12
35
(310)
+3
95 × 2P
50 - 95 × 2P
(-)
-
M12
35
(310)
95
35 - 240
(-)
-
M12
32 - 40
(283 - 354)